Permit Number | BLD17-03975 |
Status | Finaled |
Name |
GOLDEN PACIFIC TRUST SERVICES LLC
|
Site Address |
6630 W OVERLAND RD
|
Project Name | Child Care 6630 |
Customer Number | |
ePlanReview | Yes |
Description |
(CHILD CARE 6630) (CAA17-00248) 02/12/18 PLAN MODIFICATION TO REDUCE THE SMOKE ALARMS AND CO DETECTORS AND ELIMINATE EMERGENCY LIGHTING. AT LEAST ONE HARDWIRED SMOKE ALARM IS REQUIRED IN BUILDING AND IN EACH ROOM USED FOR SLEEPING IS REQUIRED TO HAVE A SMOKE ALARM. ONE CARBON MONOXIDE ALARM IS REQUIRED IF A FLAME SOURCE UTILITY IS ON THE PREMISES. JAR **This building does not have a fire sprinkler system. To convert a 1,264 square foot, one story office building to a child daycare use. Since there is only one toilet room, the total occupant load is not allowed to exceed 15 (e.g. if there are only 2 care givers then up to 13 children are allowed). Any room where children less than 2.5 years of age are cared for is required to have a door that opens directly to the outside. Smoke detectors are required in rooms used for sleeping. A carbon monoxide detector is required within this building. This building is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. **JAR**
|