Permit Information
Permit NumberBLD18-00974
StatusFinaled
Name DATUM CONSTRUCTION MANAGEMENT INC
Site Address 1301 N MILWAUKEE ST
Project NameAltitude Trampoline Park
Customer NumberBLD18-01355 EARLY START
ePlanReviewYes
Description
(ALTITUDE TRAMPOLINE PARK –WEST TENANT SPACE) The fire sprinkler system is used for unlimited area of the building and for fire area. To remodel an existing 44,436 square foot tenant space located within an existing 82,000 square foot building for a new assembly occupancy (the former use was retail sales). Interior nonstructural demolition work was done under permit BLD18-01355. Work is to include interior nonbearing walls, insulated wall furring at an exterior wall, two expanded multi-user toilet rooms accessible to the disabled, a single-user assisted-use toilet room accessible to the disabled, an elevated platform about 36 inches tall, an elevated platform about 62 inches tall, 3 interior ramps accessible to the disabled, 3 interior stairways, handrails, foam pits, trampolines, elevated platforms at jumping mats, guards, interior doors, interior windows, suspended acoustical ceilings, millwork, and finishes. The elevated platforms will be constructed of steel studs and steel joists with fire-retardant-treated wood floor sheathing. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. This permit is intended to establish a Certificate of Occupancy for this tenant. The fire sprinkler system is required to comply with NFPA 13 (including quick-response heads and foam pit sprinklers) and the fire alarm system is required to comply with NFPA 72 (including a voice alarm) as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final11/5/201811/6/201811/6/2018PPASS
DetailsMike Jordan
Cody Phone #: ###-####. Ok for perm occ. Exit sign in warehouse has been installed.
FIRE-Final Inspection11/5/201811/6/201811/6/2018APASS
DetailsTroy Cobbley
Life safety passed. Exit sign to be installed in warehouse prior to the building inspection as discussed.

Cody Phone #: ###-####
BLD-Final10/29/201810/29/201810/29/2018APART
DetailsMike Jordan
Verified work from pictures over weekend. Fire should be finaled by today. Contractor has a few transitions from handrails to clean up and will call for final whwn completed. Temp occ still ok.
BLD-Final10/26/201810/27/201810/27/2018APART
DetailsMike Jordan
Ok for temp occ. Gurad rail issues and floor transitions have issues have been resolved.
BLD-Final10/25/201810/26/201810/26/2018PNR
DetailsMike Jordan
Cody Phone #: ###-####. Needs to install all transitions from ramps to concrete floor and from 2 inch foam on elevated walkways to carpeted areas on ramps and stairs. Also noted that guardrails are only 40 inches from walking surface, Due to 2 inch foam being placed on plywood deck.
FIRE-Final Inspection10/25/201810/26/201810/26/2018APART
DetailsTroy Cobbley
A temporary for life safety is being given with the fire code and building code officials permission until the project related fire alarm permit is passed, the missing exit sign is provided in the warehouse and the racks are removed as discussed.

Cody Phone #: ###-####
FIRE-Conference10/25/201810/25/201810/25/2018PDONE
DetailsTroy Cobbley
Provide exit signs, exit discharge and emergency lights as per the approved plans, repair the existing emergency lights, provide occupant load sign, provide panic hardware where required, provide racking permit or remove racks, provide building address, remove all old fire alarm equipment and provide adequate strobe coverage with new equipment.
BLD-Conference10/23/201810/24/201810/24/2018ADONE
DetailsMike Jordan
Cody Phone #: ###-####
BLD-Framing/Rough-in10/9/201810/10/201810/10/2018APASS
DetailsMike Jordan
Ben-plat form Phone #: ###-####. Remainder of interior steel stud framed walls and cross members for elevated platforms ok to cover. Contractor also geting close to job completion. reviewed several items for final. Noted issue is the main enterance wich are power operated sliding doors. Due to Occupancy type and load, panic hardware will be required.
BLD-Framing/Rough-in10/2/201810/3/201810/3/2018APART
DetailsBrandon Shaw
High platform and access ramp farming...
Center air bag and blocking for guard rail, at later date...
BLD-Framing/Rough-in9/13/20189/14/20189/14/2018APASS
DetailsMike Jordan
partial framing for platforms prior to sheathing // Ben Phone #: ###-####. Interior steel stud framing for platforms at kids corner area.
BLD-Conference8/23/20188/24/20188/24/2018ADONE
DetailsMike Jordan
Ben Phone #: ###-####