Permit NumberBLD18-03383
StatusFinaled
Name BOISE BOMB SHELTER LLC
Site Address 600 W CURLING DR
Project NameBomb Shelter Code Upgrades
Customer Number 
ePlanReviewYes
Description
(BOMB SHELTER – CODE UPGRADES FOR OFFICE USE) A fire sprinkler system will be installed in conjunction with this permit and will be used to allow stories without exterior openings and to substitute for rated corridors. To remodel an existing 12,595 square foot building (6,375 square feet lower story and 6,220 square feet upper story) to be used for office and for music rehearsal. This building is not a public assembly occupancy. Work is to include upgrading a toilet room on the upper story to be accessible to the disabled with an accessible toilet stall and sink, installing handrails on existing stairways, and installing post-installed anchors in hardened concrete to support fire sprinkler piping. HVAC work will also be done under a separate mechanical permit to provide outside air to each room. This permit is intended to establish a Certificate of Occupancy for this tenant within this building. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department (fire sprinkler monitoring). Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final5/7/20205/8/20205/8/2020PPASS
DetailsTony Young
Jon Phone #: ###-####
FIRE-Final Inspection5/8/20205/8/20205/8/2020PPASS
DetailsJim Page
Previously noted items have been corrected, fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags. Final life fire safety inspection is complete, signatures provided on permit sign off card.



Jon *screened* Phone #: ###-####
BLD-Final5/6/20205/7/20205/7/2020PNR
DetailsTony Young
Jon Phone #: ###-####
BLD-Final5/6/20205/6/20205/7/2020PPEND
DetailsTony Young
Jon Phone #: ###-####.. needs fire/ life/saftey
BLD-Final5/5/20205/5/20205/6/2020PNR
DetailsTony Young
Jon Phone #: ###-####,, needs f/l/s
BLD-Final5/4/20205/5/20205/5/2020APEND
DetailsTony Young
Jon Phone #: ###-####// needs Fire and life safety
FIRE-Final Inspection5/4/20205/5/20205/5/2020AFAIL
DetailsJim Page
Provide exit/e,emergency light that was shown in the basement that is noted on the city approved drawings as not placed. Provide egress light in basement that is noted on the city approved drawings as not placed. Provide signage for the fire sprinkler riser room and fire alarm control panel (FACP is acceptable). Provide code compliant door hardware on two storage rooms, basement level, rooms noted on city approved drawings have round type door hardware.

Jon Phone #: ###-####
BLD-Final4/30/20205/4/20205/4/2020ANR
DetailsTony Young
Jon Phone #: ###-####// needs f/l/s and mech. 1st
BLD-Conference3/5/20203/9/20203/9/2020APART
DetailsTony Young
verify status on building/ permit,, walk through with owner,, needs trades and needs an electrical permit,, talked with concrete guys doing new steps up to the building,, work in progress
BLD-Conference3/3/20203/4/20203/5/2020PPEND
DetailsTony Young
verify status on building/ permit,, met with owner,, all is ok except needs a electrical permit and inspections,, will try to get all finaled within 2 weeks
BLD-Conference3/3/20203/3/20203/3/2020PPEND
DetailsTony Young
verify status on building/ permit// no one around