(TUCANOS BRAZILLIAN GRILL) Permit is to remodel an existing 7,995 sq. ft. restaurant. Approval is contingent upon adhering to the approved plans on file, Zoning Certificate CZC18-00261, attached design engineering and plan review report. Work to include: removal of select exterior storefront window and replace with storefront doors within the same opening, removal of exterior patio railing, removal of select concrete slab, removal of select interior nonbearing wall, removal of salad bar/grill/bar wall finish and replace with new wall finish, removal of interior booth/non-bearing column/awning, removal of kitchen FRP and replace with new FRP finish, removal of kitchen floor and install new floor waterproof membrane and finish, construction of interior design walls to create a private dining area with sliding wood doors and an openable door/door frame, new design footing foundation at the new enclosed conditioned patio area, design construction to enclose the patio area with walls and new storefront windows/door, new exterior stucco/tile finish at the patio area, repair any damaged kitchen walls, electrical work, mechanical work and interior finishes in compliance with Ch. 8 of the current IBC. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final4/10/20194/11/20194/11/2019APASS
DetailsMike Jordan
Eric Phone #: ###-####. Ok for perm occ.
BLD-Wall cover3/25/20193/26/20193/26/2019APASS
DetailsMike Jordan
eric Phone #: ###-####. Ok to cover patio area toungue and groove planking is acceptable.
BLD-Ceiling Grid Inspection3/21/20193/22/20193/22/2019PCANC
DetailsMike Jordan
Eric Phone #: ###-####
BLD-Energy code compliance3/22/20193/22/20193/22/2019PPART
DetailsMike Jordan
Eric Phone #: ###-####. Patio enclosure. Walls only ok to cover. Per the report for foam insulation, it appears that a thermal barrier is required. Will need to provide a thermal barrier or show that the 3/4 inch tongue and grove cedar will meet a 15minute barrier per NFPA 275.
BLD-Final3/13/20193/15/20193/15/2019PNR
DetailsJim Sly
for temporary occupancy // Eric Phone #: ###-####
Need Electrical final.......CDHD says that they don't want to come out.....told them.....need to verify that somehow.
FIRE-Final Inspection3/13/20193/15/20193/15/2019APASS
DetailsJim Page
Fire sprinkler inspection complete (escutcheon will be installed when painting is finished) no fire sprinkler modifications, fire extinguisher are placed with current inspection tags, hood suppression system has a current inspection tag, fire sprinkler system has a current inspection tag. Final life fire safety inspection for area of work complete.

for temporary occupancy // Eric Phone #: ###-####
BLD-Framing/Rough-in3/11/20193/12/20193/12/2019PPART
DetailsMike Jordan
patio // Eric Phone #: ###-####. Exterior wood framed walls for patio enclosure. Needs to add the missed A34's and needs electrical rough in inspection.
BLD-Wall Bracing3/8/20193/11/20193/11/2019PCANC
DetailsMike Jordan
Eric Phone #: ###-####
BLD-Framing/Rough-in3/11/20193/11/20193/11/2019PPASS
DetailsMike Jordan
Eric Phone #: ###-####. Interior framing for new wall and header for sliding glass door ok
BLD-Framing/Rough-in3/7/20193/8/20193/8/2019APART
DetailsMike Jordan
Eric if not there ask for Chris Laborde Phone #: ###-####. Interior wood framed wall for new sliding glass doors. Ok to one side. Needs to provide the attached engineering.
BLD-Energy code compliance3/6/20193/7/20193/7/2019PPASS
DetailsMike Jordan
by the foundation // Eric Phone #: ###-####
BLD-Concrete2/28/20193/5/20193/5/2019PPART
DetailsMike Jordan
call for access=footing and wall- Eric Phone #: ###-####. Footing and stemwall for patio enclosure. Ok to place pending special inspection.