Permit Information
Permit NumberBLD19-01002
StatusFinaled
Name ARTISAN CUSTOM CARPENTRY AND RENOVA
Site Address 6575 W OVERLAND RD
Project NameCaffeina
Customer Number 
ePlanReviewYes
Description
(CAFFEINA)""PLAN MODIFICATION FOR THE RELOCATION OF THE RESTROOMS AND JANITORS ROOM"" Permit is to build out for the first time a 1,360 sq. ft. restaurant tenant space (Building shell under BLD07-01506). Approval is contingent upon adhering to the approved plans on file and plan review report. Work to include: construction of interior non-bearing walls to create a janitor’s closet, two accessible restrooms and dining/kitchen area, new door/door frames, millwork, kitchen equipment, select new gypsum ceiling, light fixtures, electrical work, plumbing work, mechanical work and interior finishes in compliance with Ch. 8 of the current IBC. This building is Not Fire Sprinklered. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final8/21/20198/21/20198/21/2019PPASS
DetailsMike Jordan
Sorry for the re inspections. Kris has appropriate signage and it will be up by noon. Thanks Phone #: ###-#### Inspection requested via web by Ryan Allen. All issues resolved. Ok for perm occ.
BLD-Final8/20/20198/20/20198/20/2019PFAIL
DetailsMike Jordan
Re inspection for full c.o.
Thanks Phone #: ###-#### Inspection requested via web by Ryan Allen. All issues resolved except for the ADA bathroom signage. Provided signage is not ADA compliant.
BLD-Final8/11/20198/12/20198/12/2019PPART
DetailsMike Jordan
Kris will be the onsite contact for this. His number is above.
Thanks Phone #: ###-#### Inspection requested via web by Ryan Allen. Post building address. Install ADA bathroom signs. Provide ADa compliant mirrors in bathrooms. Correction notice issued. Ok for temp. occ.
FIRE-Final Inspection8/11/20198/12/20198/12/2019APASS
DetailsJim Page
Previously noted items have been corrected, no fire sprinklers, no fire alarms, fire extinguishers are placed with current inspection tags, addressing will be installed before BLD final. Final life fire safety inspection for area of work complete.

Kris will be the contact for this inspection. Phone #: ###-#### Inspection requested via web by Ryan Allen
FIRE-Final Inspection8/6/20198/6/20198/6/2019PFAIL
DetailsTroy Cobbley
Provide single action hardware on the south exit door as per plans and provide testing of the exit lights/emergency lights/exit discharge lights.

Kris will be the on site contact for this. Please call him prior to your coming so he can be sure to be there.
Thanks Phone #: ###-#### Inspection requested via web by Ryan Allen
BLD-Energy code compliance7/9/20197/9/20197/9/2019PPASS
DetailsMike Jordan
Insulation will be completed by about 3. Hopefully this will work in your schedule. Thanks Phone #: ###-#### Inspection requested via web by Ryan Allen
BLD-Framing/Rough-in7/8/20197/9/20197/9/2019APASS
DetailsMike Jordan
Inspection of framing for new interior walls Phone #: ###-#### Inspection requested via web by Ryan Allen. Ok to insulate.
BLD-Framing/Rough-in7/8/20197/8/20197/8/2019ACANC
DetailsMike Jordan
Inspection of new framing in T.I. project.
Thanks Phone #: ###-#### >> Inspection requested via web by Ryan Allen Inspection cancelled from web by: Ryan Allen
BLD-Conference6/13/20196/14/20196/14/2019ADONE
DetailsMike Jordan
We would like ok to hang double 5/8 sheetrock to area of fire wall where we will later frame perpendicular walls onto. No plumbing or electrical or HVAC is embedded within this portion of wall. Please call Kris, the contact for this ###-####. He can meet you if needed. Key box code on door is 1127.
Thank you Phone #: ###-#### Inspection requested via web by Ryan Allen