BLD-Final | 3/26/2020 | 3/27/2020 | 3/27/2020 | P | PASS |
Jim Storey
|
|
|
Please call 30 minutes before hand for access to fire riser room. Phone #: ###-#### Inspection requested via web by Stephen Griswold
|
DOC - Permit Finaled | 3/27/2020 | 3/27/2020 | 3/27/2020 | P | PASS |
Jim Storey
|
|
|
|
FIRE-Final Inspection | 3/25/2020 | 3/26/2020 | 3/26/2020 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed. Call for access/site meeting. Phone #: ###-#### Inspection requested via web by Stephen Griswold
|
FIRE-Final Inspection | 3/25/2020 | 3/25/2020 | 3/25/2020 | P | FAIL |
Troy Cobbley
|
|
|
Need city approved plans an dsmall documents, need smoke alarms placed and tested as discussed, need fire extinguisher placed as discussed. Need address as discussed.
NEED FINAL LIFE SAFETY COMPLETED; WAS NOT DONE DURING INITIAL FIRE FINAL INSPECTION Phone #: ###-#### Inspection requested via web by Stephen Griswold
|
BLD-Final | 3/24/2020 | 3/24/2020 | 3/24/2020 | P | CANC |
Jim Storey
|
|
|
Please call prior to inspection to coordinate access. Phone #: ###-#### >> Inspection requested via web by Stephen Griswold Inspection cancelled from web by: Stephen Griswold
|
BLD-Final | 1/3/2020 | 1/3/2020 | 1/3/2020 | P | FAIL |
Jim Storey
|
|
|
Phone #: ###-#### Inspection requested via web by Stephen Griswold need fire and hvac finals
|
FIRE-Final Inspection | 1/3/2020 | 1/3/2020 | 1/3/2020 | P | CANC |
Troy Cobbley
|
|
|
Need fire alarm and sprinkler permits addressed as per discussion before life safety inspection can be completed.
Phone #: ###-#### Inspection requested via web by Stephen Griswold
|
BLD-Framing/Rough-in | 9/30/2019 | 9/30/2019 | 9/30/2019 | P | PART |
Jim Storey
|
|
|
Phone #: ###-#### Inspection requested via web by Stephen Griswold INSP-Sprinkler Rough-in 9/26/2019 9/27/2019 9/27/2019 P PART
DetailsTroy Cobbley Tenting failed for all areas. No piping to be covered. Rough-in passed for the single level area of work but again no piping can be covered. Also prior to a final inspection R38 insulation value will need to be provided. framing ok to cover upon passing fire insp.
|
BLD-Framing/Rough-in | 9/5/2019 | 9/5/2019 | 9/5/2019 | P | FAIL |
Jim Storey
|
|
|
need fire chakl per plan/ need hvac permit and insp./ fire spk insp// group all permits to bld.
|
BLD-Framing/Rough-in | 9/4/2019 | 9/4/2019 | 9/4/2019 | P | NR |
Jim Storey
|
|
|
Phone #: ###-#### Inspection requested via web by Stephen Griswold
|
BLD-Framing/Rough-in | 8/6/2019 | 8/6/2019 | 8/6/2019 | P | FAIL |
Jim Storey
|
|
|
Phone #: ###-#### Inspection requested via web by Stephen Griswold c/n arch to address conf with builder.
|