BLD-Final | 3/13/2020 | 3/16/2020 | 3/16/2020 | A | PASS |
Jim Storey
|
|
|
Marcus Phone #: ###-####
|
FIRE-Final Inspection | 3/13/2020 | 3/13/2020 | 3/13/2020 | P | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, annual inspection for fire sprinklers is current, fire panel is normal with 2 lines of communication, fire extinguishers are placed with current inspection tags. Final life fire safety inspection is complete, signature card not available at time of inspection.
Marcus Phone #: ###-####
|
BLD-Final | 7/1/2019 | 7/2/2019 | 7/2/2019 | A | NR |
Jim Storey
|
|
|
Jerad Phone #: ###-####
|
FIRE-Final Inspection | 7/1/2019 | 7/1/2019 | 7/1/2019 | P | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for list of corrections that include repairing exit signs and emergency lights, adding exit signs and emergency ?lights, providing annual inspection for the fire extinguishers, adding/approval of the two exterior rooms under the east side canopy, repairing the fire alarm panel...ect
Jerad Phone #: ###-####
|
FIRE-Final Inspection | 6/10/2019 | 6/11/2019 | 6/11/2019 | A | FAIL |
Jim Page
|
|
|
Under a previous tenant notes (BLD17-01333) it was noted that some overhead doors did not have fire sprinkler protection under the roll up type doors which is required by NFPA13. The heads were added but no permit was issued. A permit needs to be issued, inspected and passed before life fire safety inspection for this permit can be completed. Reference notes under BLD17-01333 for defecincies that were noted on 7/12/2017 and 4/19/2018.
Ross Phone #: ###-####
|