Permit Information
Permit NumberBLD19-02216
StatusIssued
Name EIGHTH & MAIN CONDOMINIUM ASSOCIATI
Site Address 800 W MAIN ST Unit: 210
Project NameBlackBox VR T.I.
Customer Number 
ePlanReviewYes
Description
(BLACKBOX VR - GARDNER COMPANY SUITE #210) This building is fire sprinkled as it is a high rise. Permit to remodel 2,667 sqft. of existing recreational space to create a virtual reality gym. Work to include: demo select interior non-load bearing walls and door, construct new non-load bearing wall to create new IT closet and infill wall, 8'-0" partition system to separate gym space, minor electrical work. Interior finishes shall be in compliance with chapter 8. Approval is contingent on adhering to the approved plans. Any alterations or modifications to the buildings fire sprinkler or fire alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise fire Department. MDH
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final8/2/20198/2/20198/2/2019PPASS
DetailsDave Hannah
Laren Phone #: ###-####
FIRE-Final Inspection8/2/20198/2/20198/2/2019PPASS
DetailsJim Page
Fire sprinkler inspection is complete, fire alarm inspection is complete, outlets for VR units shunt during fire alarm activation, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.
BLD-Final7/31/20198/1/20198/1/2019PCANC
DetailsTell Riley
Leren Phone #: ###-####//cancel per Leren//need to pass fire final//
FIRE-Final Inspection7/31/20198/1/20198/1/2019AFAIL
DetailsMark Scharfen
E-lights/extinguisher in place. Tested interface for shunt with Protex on site. Manually turning on relay did shunt the breaker but did not work in normal operation. Told Leren and Protex that a fire alarm permit would need to be pulled and proof of a propper pretest before building or fire alarm final is to be called in again.

Leren Phone #: ###-####
DOC - Permit Finaled7/31/20197/31/20197/31/2019PPASS
DetailsDave Hannah