Permit Information
Permit NumberBLD19-03936
StatusFinaled
Name SAWTOOTH CONSTRUCTION GROUP INC
Site Address 3050 N LAKEHARBOR LN Unit: 201
Project NameGreat West Engineering Ste 201
Customer Number 
ePlanReviewYes
Description
(GREAT WEST ENGINEERING – SUITE #201) Permit to combine an existing 2,219 sq. ft. office tenant space with the adjacent 866 sq. ft. office tenant space to create a new office tenant space that is 3,085 sq. ft. within the 2nd floor of the existing building. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of interior nonbearing walls, removal of select door/door frames, removal of millwork, construction of interior non-bearing walls, select new door/door frames, electrical work, plumbing work and interior finishes in compliance with Ch. 8 of the 2015 IBC. This building is fully Fire Sprinklered for area increase. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/22/20201/23/20201/23/2020PPASS
DetailsTony Young
Phone #: ###-#### Inspection requested via web by Kirsten Dallmann
FIRE-Final Inspection1/22/20201/23/20201/23/2020APASS
DetailsJim Page
Previously noted item has been corrected, fire sprinkler inspection is complete, a full fire alarm replacement is issued for this building under FIR19-00522, will verify fire alarm coverage during the final inspection for mentioned FIR permit, fire extinguishers are placed with current inspection tags. Final life fire safety inspection for area of work complete.

Final fire after sprinklers have been removed. Phone #: ###-#### Inspection requested via web by Kirsten Dallmann
FIRE-Final Inspection1/14/20201/15/20201/15/2020AFAIL
DetailsJim Page
2 areas have fire sprinklers that are less than 6 feet apart, fire sprinkler modifications are required for area of work to be compliant with NFPA13. Any and all fire sprinkler modifications requires a seperate permit.

are will be onsite after 9am. Phone #: ###-#### Inspection requested via web by Kirsten Dallmann
BLD-Framing/Rough-in12/11/201912/12/201912/12/2019APART
DetailsTony Young
Combining of Suites 201 and 205. Phone #: ###-#### Inspection requested via web by Kirsten Dallmann// walls ok after bracing tops per plan