Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberBLD19-04891
StatusFinaled
Name MCCARTER-MOORHOUSE LLC
Site Address 7800 W USTICK RD Unit: 100
Project NameDr. Paige Schmidt TI
Customer Number 
ePlanReviewYes
Description
(BAY POINTE DENTAL CENTER BLDG. #1 - DR. PAIGE SCHMIDT T.I.) 04-06-2020 PLAN MODIFICATION CLARIFICATION MADE TO THE CONSTRUCTION OF THE MED GAS ROOM. This building is fire sprinkled. Permit to remodel an existing 2,800 sqft. office space for use as a dental office. Work to include: demo non-bearing interior walls, construct non-bearing interior walls, new lighting, new finishes, mechanical work, electrical work, and plumbing work. 1 hour fire rated walls required at med gas closet. Interior finishes shall be in compliance with Ch. 8 of the 2015 IBC. This building is fully fire sprinkled. Any alterations or modifications to the buildings fire sprinkler or fire alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise fire department. **MDH**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final5/11/20205/11/20205/11/2020PPASS
DetailsTell Riley
I would like to meet you onsite to review.

Dana McCarter
###-#### Phone #: ###-#### Inspection requested via web by Drew Moorhouse//final ok see notes below//add second microwave that is in an accessible location or lower the one onsite//letter from architect needs to be submitted and added to documents for project//
FIRE-Final Inspection5/8/20205/11/20205/11/2020APASS
DetailsTroy Cobbley
Life safety passed.

I would like to meet you onsite.

Thanks,
Dana Phone #: ###-#### Inspection requested via web by Drew Moorhouse
FIRE-Final Inspection5/7/20205/8/20205/8/2020AFAIL
DetailsTroy Cobbley
Life safety will be ok to sign off when the project related fire alarm permit is finaled.

I would like to meet onsite to review any corrections if need be.

Thanks,
Dana McCarter
###-#### Phone #: ###-#### Inspection requested via web by Drew Moorhouse
BLD-Conference4/29/20204/30/20204/30/2020PDONE
DetailsTell Riley
meet Drew ###-####//discuss med gas room, need architect to approve as built design, 2x6 wall does not extend to underside of roof deck, although shaft is lined with 2 layers 5/8 typ X, walls below are 2x6 with 5/8 type x on both sides//does not match plans//
BLD-Ceiling Grid Inspection4/28/20204/29/20204/29/2020PPASS
DetailsTell Riley
I would like to meet you onsite to review any correction if need be.

Thanks,
Drew Moorhouse
McCarter-Moorhouse
###-####


Phone #: ###-#### Inspection requested via web by Drew Moorhouse// fix insulation above exam area//add clips to wall connections in back room, other wise ok to cover grid//will meet Drew thursday regarding med gas room and fire wall//
BLD-Framing/Rough-in3/16/20203/16/20203/16/2020PPASS
DetailsTell Riley
Phone #: ###-#### Inspection requested via web by Drew Moorhouse//wall cover only//do not cover med gas room, or area needing sprinklers moved//
BLD-Conference3/13/20203/16/20203/16/2020ADONE
DetailsTell Riley
We would like to meet onsite at 10AM Phone #: ###-#### Inspection requested via web by Drew Moorhouse
BLD-Conference3/13/20203/13/20203/13/2020PDONE
DetailsTell Riley
requested by Mech inspector to look at med gas room//CN posted for contractor to contact me for conference regarding med gas room ratings and construction//
BLD-Framing/Rough-in3/2/20203/3/20203/3/2020ANR
DetailsBrandon Shaw
Need grades...