INSP - Final | 8/29/1997 | 8/29/1997 | 8/29/1997 | | PASS |
Jim Storey
|
|
|
/ / 301 - FNL -OK FINAL
|
INSP-Final Inspection | 8/29/1997 | 8/29/1997 | 8/29/1997 | P | PASS |
Rick Jackson
|
|
|
|
Permanent Occupancy | | 8/29/1997 | 8/29/1997 | | DONE |
|
|
|
|
INSP - Final | 8/26/1997 | 8/27/1997 | 8/27/1997 | P | NR |
Jim Storey
|
|
|
08/27/97 301 - i gave floyd his for 8/26/97 all other trades finaled. ca CORR-CORREC-CALL FOR REINSP WHEN COMPLETED HI JIM.....I FAILED THEM TUESDAY PM, ALARM ZONES STILL NOT RIGHT
|
INSP-Final Inspection | 8/26/1997 | 8/26/1997 | 8/26/1997 | P | FAIL |
|
|
|
cathy has card to sign off. ALARM RESPONCE STILL WRONG ( 5/23 CORRECTION LIST) FD CALLED FOR EVERYTHING... TO CORRECT ASAP
|
INSP - Final | 5/29/1997 | 5/29/1997 | 5/29/1997 | | PASS |
Jim Storey
|
|
|
/ / 301 - TCO -TEMP C OF O ISSUED CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
|
INSP - Final | 5/23/1997 | 5/27/1997 | 5/27/1997 | P | NR |
Jim Storey
|
|
|
05/27/97 301 -
|
INSP-Final Inspection | 5/23/1997 | 5/23/1997 | 5/23/1997 | P | PART |
|
|
|
supervisorys still tranmit as alarms, need nfpa 72
|
INSP-Final Inspection | 5/21/1997 | 5/21/1997 | 5/21/1997 | P | FAIL |
|
|
|
address not visible, piv not monitored, all signals transmit as fire alarms, panel troubles do not transmit, 1 head too close to unit heater for temp rating
|
INSP-Final Inspection | 5/12/1997 | 5/12/1997 | 5/12/1997 | P | FAIL |
|
|
|
c/n issued, lots of details to wrap up, advised egress control devices must have auto, manual, fire alarm and power out release
|
INSP - Framing/Rough-in | 5/9/1997 | 5/9/1997 | 5/9/1997 | P | PASS |
Jim Storey
|
|
|
05/09/97 301 - FRAM-OK FRAMING Resubmital wall
|
INSP - Framing/Rough-in | 4/24/1997 | 4/25/1997 | 4/25/1997 | A | PASS |
Jim Storey
|
|
|
04/25/97 301 - ceiling wall SCLG-OK SUSPENDED CEILING and draft stop ok
|
INSP-Sprinkler Rough-in/Hydro | 4/24/1997 | 4/25/1997 | 4/25/1997 | A | PASS |
|
|
|
hydro test, todd will call when pressurized replaced test orifice w/ correct size
|
INSP-Sprinkler Rough-in/Hydro | 4/24/1997 | 4/24/1997 | 4/24/1997 | A | PART |
|
|
|
correction list given to herb on missing sprinklers. also gave notice that approved plans do not allow storage over 12 ft. sprinklers designed for 16 ft, no racks over 8 ft since no seismic was provided
|
INSP-Sprinkler Rough-in/Hydro | 4/23/1997 | 4/23/1997 | 4/23/1997 | P | PART |
|
|
|
herb dock area not complete, need to check 2nd floor storage
|
INSP - Conference | 4/21/1997 | 4/21/1997 | 4/21/1997 | | PART |
Jim Storey
|
|
|
/ / 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
|
INSP - Carpentry | 4/3/1997 | 4/2/1997 | 4/3/1997 | | PASS |
Jim Storey
|
|
|
sheer nailling on walls
|
INSP - Framing/Rough-in | 4/1/1997 | 4/1/1997 | 4/1/1997 | P | PASS |
Jim Storey
|
|
|
sheer nailling ok mezanine fr ok
|
INSP - Framing/Rough-in | 3/25/1997 | 3/25/1997 | 3/25/1997 | P | PART |
Jim Storey
|
|
|
03/25/97 301 - INTER STUD WALLS ALL BUT SHEER OK
|
INSP - Footings | 3/11/1997 | 3/12/1997 | 3/12/1997 | P | PASS |
Jim Storey
|
|
|
03/12/97 301 - covered by si. recieved eifs submital and approved system
|
INSP - Foundation | 12/12/1996 | 12/13/1996 | 12/13/1996 | A | PASS |
Jim Storey
|
|
|
12/13/96 301 - CALLED IN A FLOOR POUR FDN -OK FOUNDATION hair pins
|
INSP - Footings | 11/26/1996 | 11/27/1996 | 11/27/1996 | P | PASS |
Jim Storey
|
|
|
/ / 301 - READY AT 1PM PLEASE. FRMS-OK FORMS-REBAR special insp on site
|
INSP - Footings | 11/26/1996 | 11/26/1996 | 11/26/1996 | P | PART |
Jim Storey
|
|
|
11/26/96 301 - WIP -WORK IN PROGRESS special insp. on site pending repor
|
INSP - Footings | 11/25/1996 | 11/25/1996 | 11/25/1996 | P | NR |
Wes Worcester
|
|
|
still placing dobbies and getting side clearance...spec insp to be on site
|
INSP - Foundation | 11/25/1996 | 11/25/1996 | 11/25/1996 | P | PART |
Wes Worcester
|
|
|
poured with special insp on site...pending report as some dowels had less than 1" cover between them at jambs
|
INSP - Foundation | 11/21/1996 | 11/21/1996 | 11/21/1996 | P | PART |
Wes Worcester
|
|
|
special insp on site
|
INSP - Conference | 11/19/1996 | 11/19/1996 | 11/19/1996 | A | PASS |
Wes Worcester
|
|
|
ck on lean concrete fill - going to pour at 3pm w/sp insp
|
INSP - Footings | 11/19/1996 | 11/19/1996 | 11/19/1996 | P | PASS |
Wes Worcester
|
|
|
APPT. 3 P.M.
|
INSP - Footings | 11/19/1996 | 11/19/1996 | 11/19/1996 | A | NR |
Wes Worcester
|
|
|
|
INSP - Site Preparation | 11/19/1996 | 11/19/1996 | 11/19/1996 | A | PART |
Wes Worcester
|
|
|
cleaning out mud and having soils tested
|
INSP - Footings | 11/14/1996 | 11/15/1996 | 11/15/1996 | A | FAIL |
Wes Worcester
|
|
|
inadequate cover, special inspectors report rejected, eng of record and special inspector to meet on site. several 100'poured
|