Permit Information
Permit NumberBLD96-03234
StatusFinaled
Name MOTEL 6
Site Address 2323 W AIRPORT WAY
Project Name 
Customer Number 
ePlanReviewNo
Description
(MOTEL 6) To remodel interior with minimum exterior changes to an existing 91 unit motel in 3 SECTIONS per approved plans on file. The SECTIONS are as follows: SECTION 1 - 32 UNITS OF BUILDING A; SECTION 2 - 15 UNITS OF BUILDING B AND THE EAST 12 UNITS OF BUILDING C; SECTION 3 - WEST 32 UNITS OF BUILDING C. Work to include replacement of all exterior windows, dividing up storage room on 1st floor of Bldg. A to create new laundry facility, install new cabinetry in the Manager's office, install new safety glass sidelight adjacent to door between vestibule and lobby of Manager's office, construct storage area under the southern stairway in Building A, remodel rooms 12, 18, 80 and 84 to create accessible units for the physically disabled, and replacement of shower stalls, sinks, toilets, replacement of all doors and hardware to rooms and miscellaneous finish in all units. (Note: Interior demolition issued under BLD96-3241) (P.C.#732-96) FIRE ALARM SYSTEM TO COMPLY WITH FIRE DEPARTMENT COMMENTS ATTACHED TO PLANS. prp (2/14/97 - This permit revised to designate building sections by M. Southard.)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in/Hydro10/1/199710/1/199710/1/1997PPASS
DetailsRick Jackson
MOTEL 6--FIRE LIFE SAFETY Follow up inspection of open c/n items.
INSP - Final9/30/19979/30/199710/1/1997PPART
DetailsJim Storey
09/30/97 301 - perm. occ ok upon plm. and fire sign offs
INSP - Final5/20/19975/21/19975/21/1997ANR
DetailsJim Storey
05/21/97 301 -
INSP-Final Inspection5/21/19975/21/19975/21/1997PFAIL
Details
alarms not tested, handicap rooms alarm entire building, fe cabinets locked, understair storage not prot by 1 hr, no plans on site, KNOX BOX??
INSP - Foundation5/20/19975/20/19975/20/1997PPASS
DetailsJim Storey
05/20/97 301 - REBAR IN FOUNDATION OF POOL HOUSE FRMS-OK FORMS-REBAR
INSP - Footings5/15/19975/16/19975/16/1997PPASS
DetailsJim Storey
05/16/97 301 - MOTEL 6/ POOL ROOM/ EARLY PM PLEASE/ DON BUCKMASTER/ 322- CFRM-OK CEILING FRAMINGO CALL YOU TO SCHEDULE TIME
INSP - Ceiling grid4/21/19974/22/19974/22/1997APASS
DetailsJim Storey
04/22/97 301 - SCLG-OK SUSPENDED CEILING
INSP - Ceiling grid4/21/19974/21/19974/21/1997 FAIL
DetailsJim Storey
/ / 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED n/r for complet insp and menb protection must be in place before tile cover.
INSP - Ceiling grid4/21/19974/21/19974/21/1997PFAIL
DetailsJim Storey
T-BAR GRID and membrane protection not complet.
INSP - Framing/Rough-in3/31/19974/1/19974/1/1997APART
DetailsJim Storey
04/01/97 301 - FRAM-OK FRAMING ADA ROOMS 3 OUT OF 4
INSP - Carpentry3/18/19973/18/19973/18/1997PPASS
DetailsJim Storey
03/18/97 301 - fire caulking GWB -OK SHEETROCK NAILING fire stopping at bath 1 st floor c wing ok
INSP - Carpentry3/13/19973/14/19973/14/1997APART
DetailsJim Storey
03/14/97 301 - FIRE CAULK WIP -WORK IN PROGRESS ok valve assembly 2nd floor.
INSP - Carpentry3/10/19973/11/19973/11/1997APASS
DetailsJim Storey
03/11/97 301 - putty pads in place on upper units a wing ok
INSP - Final3/10/19973/10/19973/10/1997PPART
Details
section 1 temp, ok,back of card signed
INSP-Conference3/10/19973/10/19973/10/1997PPART
Details
return alarm plans, not complete, grinnel to provide batt and volt drop calcs, removing h/c detectors from building alarm
INSP - Carpentry2/12/19972/13/19972/13/1997APASS
DetailsJim Storey
02/12/97 301 - FIRE STOP (AFTR 9 A.M.) FRBL-OK FIREBLOCKING
INSP - Carpentry2/7/19972/10/19972/10/1997PPASS
DetailsJim Storey
02/10/97 301 - FIRE CAULKING, ETC. GWB -OK SHEETROCK NAILING
INSP - Carpentry2/7/19972/7/19972/7/1997 PASS
DetailsJim Storey
02/07/97 301 - FIRE STOPS FRWL-RATED WALL CONST. OK
INSP - Final2/5/19972/5/19972/5/1997AFAIL
Details
issue c/n after researching plans and talking with dick pierce. wing "C" only inspected. lots of problems...rated doors not installed to corridor, deadbolts on exit doors, alarms, exit signs, fire extinguishers locked up, storage under stairs.
INSP - Temporary occupancy2/5/19972/5/19972/5/1997PNR
DetailsJim Storey
02/05/97 301 - n/r
INSP - Final2/4/19972/4/19972/4/1997PFAIL
Details
exit hardware wrong, alarms not upgraded in c wing as required, want to do in phases but not noted on plans, no emergency power for exit lights..no plan review comments, will look up in vault
INSP - Carpentry1/6/19971/6/19971/6/1997PPART
DetailsJim Storey
01/06/97 301 - fire stopping on first 6/lower and 4 upper ok at shower v
INSP - Carpentry1/3/19971/6/19971/6/1997APART
DetailsJim Storey
01/06/97 301 - fire stopping first group of rooms 3 n top/bottom west en assembly
INSP-Conference1/3/19971/3/19971/3/1997 PASS
Details
/ / 405 - reviewed alarm system requirements w/ contractor. need hall H/S. rooms need single sta smokes, ada romms need h/s.
INSP - Framing/Rough-in12/30/199612/30/199612/28/1996PNR
Details
12/30/96 338 -