Permit Information
Permit NumberBLD96-03313
StatusFinaled
Name LES BOIS HIGH SCHOOL
Site Address 701 E BOISE AVE
Project NameSCHOOL
Customer Number 
ePlanReviewNo
Description
LES BOIS HIGH SCHOOL * THE PROJECT CONSISTS OF ADDITIONS TO THE EXISTING BUILDING WHICH INCLUDES A TWO STORY CLASSROOM/OFFICE AREA, A NEW GYMANSIUM AND NEW THEATER. THE CLASSROOM\OFFICE AND GYMANSIUM ADDITION WILL BE A 38060 SQ. FT. TYPE II-1HR BUILDING WITH THE THEATER BEING A 11,200 SQ. FT. TYPE II-FR BUILDING. ALL AREAS SHALL BE FULLY FIRE SPRINKLERED. OTHER WORK INCLUDES INTERIOR REMODELING, LANDSCAPE DEVELOPMENT, SITE DRAINAGE UTILITIES, PAVING AND OTHER SITE WORK PER PLANS AND APPROVAL BY PUBLIC WORKS. ALL WORK IS PER APPROVED PLANS AND ATTACHMENTS, CU#-95-95,PC#752-96 FIRE SPRINKLERS USED FOR AREA. NOTE: NEW BLEACHERS FOR THE GYM ARE NOT INCLUDED UNDER THIS PERMIT AND A SEPARATE PLAN REVIEW AND PERMIT IS REQUIRED PIROR TO INSTALLING.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Occupancy 11/30/199811/30/1998 DONE
Details
INSP - Final10/7/199810/7/199810/7/1998 PASS
DetailsJim Storey
/ / 301 - achrived final letter from engineer of reccord and special i
INSP - Final9/10/19989/10/19989/10/1998PPASS
DetailsJim Storey
09/10/98 301 - keith ###-#### FNL -OK FINAL
INSP-Final Inspection9/10/19989/10/19989/10/1998PPASS
DetailsRick Jackson
KEITH ###-#### occ approved
INSP-Final Inspection9/8/19989/9/19989/9/1998PFAIL
DetailsRick Jackson
KEITH ###-#### FN PER RICK AT 3:00 no access for dampers - retest after doors installed
INSP - Final8/28/19988/28/19988/28/1998 PART
DetailsJim Storey
08/28/98 301 - TEMP OCC /KEITH ###-#### CORR-CORREC-CALL FOR REINSP WHEN COMPLETED OK FOR TEMP OCC. ON GYM AND 2 FLOOR CLASS ROMMS ONLY. A2.1 IS NOT TO BE OCCUPIED AND HAS SEPERATE OCC
INSP-Final Inspection8/20/19988/20/19988/20/1998PPART
DetailsRick Jackson
temp occ approved for gym/classroom only. strobes in classrooms 301 and 307 need repair
INSP - Final8/18/19988/18/19988/18/1998PFAIL
DetailsJim Storey
08/18/98 301 - Scheduled by Hello!. CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP - Final8/5/19988/6/19988/6/1998PPASS
DetailsJim Storey
08/06/98 301 - stage curtin release test 21 sec meets code and listing f verified 165* assembley approved.
INSP-Final Inspection8/6/19988/6/19988/6/1998PPART
DetailsRick Jackson
tested stage curtain - 21 second drop time. installed per manufacturers instructions.
INSP-Sprinkler Rough-in/Hydro7/22/19987/23/19987/23/1998PPASS
DetailsRick Jackson
doug ###-#### hydro and rough-in for auditorium - NE riser hydro okay. gaurds still needed in pit area (auditorium).
INSP - Framing/Rough-in7/15/19987/16/19987/16/1998APASS
DetailsJim Storey
07/16/98 301 - Scheduled by Hello!. FRAM-OK FRAMING ceilling at adatormum north east corner ok for cover at exterior vestabual. ì
INSP - Framing/Rough-in7/8/19987/9/19987/9/1998AFAIL
DetailsJim Storey
07/09/98 301 - Scheduled by Hello!. CORR-CORREC-CALL FOR REINSP WHEN COMPLETED stair internint hand rail req
INSP - Framing/Rough-in7/2/19987/2/19987/3/1998PPART
Details
07/02/98 333 - bathrooms ok
INSP - Framing/Rough-in6/29/19986/30/19986/30/1998APART
Details
framing ok insp. done 6/29/98 301 c/n posted for insp. at ceilling.
INSP - Framing/Rough-in6/24/19986/25/19986/26/1998PPART
DetailsJim Storey
06/24/98 301 - Scheduled by Hello!. FRAM-OK FRAMING
INSP-Alarm Testing6/16/19986/16/19986/16/1998PFAIL
DetailsRick Jackson
wrong strobes (15/75 instead of 75) in numerous areas. c/n issued with list of items needed for temp occ.
INSP-Final Inspection6/12/19986/15/19986/15/1998PNR
DetailsRick Jackson
FINAL READY AT 1 DOUG/ ###-#### N.PAGER NR for alarm test. conducted rough-in of auditorium and associated rooms - not complete. alarm test scheduled for 6/16 by electrical contractor
INSP - Framing/Rough-in6/8/19986/9/19986/9/1998APART
DetailsJim Storey
06/09/98 301 - entry to adatorum fire rated const. and opening ok
INSP - Framing/Rough-in5/15/19985/18/19985/18/1998APASS
DetailsJim Storey
05/18/98 301 - recieved resubmital for detail e1/bs7.3 to reduce welding
INSP - Framing/Rough-in5/13/19985/14/19985/14/1998AFAIL
DetailsJim Storey
05/14/98 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED welds at curti
INSP - Framing/Rough-in5/5/19985/5/19985/5/1998 PASS
DetailsJim Storey
05/05/98 301 - FRAM-OK FRAMING strucral wall east side of audatotim
INSP - Framing/Rough-in5/4/19985/5/19985/5/1998APASS
DetailsJim Storey
05/05/98 301 - FRAM-OK FRAMING struc. east of adatoraum
INSP - Framing/Rough-in4/28/19984/28/19984/28/1998APART
DetailsJim Storey
04/28/98 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED ok for celling
INSP - Framing/Rough-in4/27/19984/27/19984/28/1998PPASS
DetailsJim Storey
04/27/98 301 - SCLG-OK SUSPENDED CEILING
INSP-Sprinkler Rough-in/Hydro4/22/19984/22/19984/22/1998APASS
DetailsRick Jackson
rough-in for gym and class areas. okay to cover with tiles. told contractor to leave access for dampers.
INSP-Final Inspection4/21/19984/21/19984/21/1998PCANC
DetailsJoe Tawney
04/21/98 406 - doug ###-#### pager put in your number CANCELLED TO BE DONE BY 405
INSP-Sprinkler Rough-in/Hydro4/21/19984/21/19984/21/1998 PART
Details
witnessed at 205 after 2 hrs...pump was left connected during test. told Doug NOT to do this again. Not testing from control valve to system connection.
INSP - Framing/Rough-in4/13/19984/13/19984/14/1998PFAIL
DetailsJim Storey
04/13/98 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETEDOTHER INSP. REQ
INSP - Framing/Rough-in3/25/19983/26/19983/26/1998APART
DetailsJim Storey
03/26/98 301 - STEEL STUDED FOR AUDITORIUM RADIUS-WES ###-#### VOICE PAGER 10:00 appointment with arch. discuss fire door isue framing ok at west s
INSP - Framing/Rough-in3/18/19983/19/19983/20/1998APART
DetailsJim Storey
03/20/98 301 - ceiling inspection wes ###-#### pager south entry ok for cover and west stair at landing
INSP-Sprinkler Rough-in/Hydro3/19/19983/19/19983/19/1998PPART
DetailsRick Jackson
DOUG PAGER ###-####--LES BOIS--HE WILL CALL YOU rough-in only. okay to cover 1st floor corridor and stairwell.
INSP - Framing/Rough-in2/23/19982/24/19982/24/1998PFAIL
DetailsJim Storey
02/24/98 301 - wes cell ###-#### grid ceiling insp
INSP - Framing/Rough-in2/17/19982/17/19982/17/1998PNR
DetailsBob Archibald
###-#### HARD CEILING
INSP - Framing/Rough-in2/11/19982/12/19982/12/1998APART
DetailsJim Storey
02/11/98 301 - WES PAGER ###-#### CORR-CORREC-CALL FOR REINSP WHEN COMPLETED ok to proceed can verify at n insp.
INSP - Framing/Rough-in2/4/19982/5/19982/5/1998APASS
DetailsJim Storey
02/05/98 301 - CEILING IN DOWNSTAIR HARD LID AREAS--WES AT ###-#### PAGE FRAM-OK FRAMING /pending mti fireproofing approval.
INSP-Sprinkler Rough-in/Hydro2/4/19982/5/19982/5/1998APASS
DetailsRick Jackson
02/05/98 409 - READY AT 11:00--DOUG AT ###-#### PAGER approved sprinkler plans on site. completed hydro and rough-in.
INSP - Conference2/2/19982/2/19982/2/1998 PART
DetailsJim Storey
/ / 301 - fire stopping for 2hr area wall submital not complet work is requier investagation of proper assembly upon submital of product listin contractor and bldg. dept..// fire stopping for one hour roof/ceilling assembly not done at this t
INSP - Framing/Rough-in1/20/19981/21/19981/22/1998PPART
DetailsJim Storey
01/21/98 301 - ###-#### WES\LES BOIS HIGH SCHOOL trans to tom he called and said that gyp nailling ok
INSP - Framing/Rough-in1/14/19981/15/19981/15/1998APART
DetailsJim Storey
01/14/98 301 - LES BOIS JUNIOR HIGH--KEITH ###-#### 2nd floor class rooms and coridor ok for cover up to stairs. drinking fo and door assem. not instaled or insp for membrane penatrations of corido
INSP - Framing/Rough-in1/8/19981/13/19981/13/1998APART
DetailsJim Storey
01/13/98 301 - rein WIP -WORK IN PROGRESS ok to gyp corrodor one side before reinsp.
INSP - Wall cover1/7/19981/8/19981/9/1998APART
DetailsRuss Owen
01/08/98 407 - Went with 301 to job and left corrections.
INSP - Framing/Rough-in1/8/19981/8/19981/8/1998 FAIL
DetailsJim Storey
/ / 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED ok to one side only.
INSP - Framing/Rough-in12/19/199712/19/199712/19/1997 PART
DetailsJim Storey
12/19/97 301 - 2 nd floor gym rated ceilling and shafts ok all but 2 wer flue.
INSP - Framing/Rough-in12/19/199712/19/199712/19/1997 PART
DetailsJim Storey
12/19/97 301 - 2 nd floor gym rated ceilling and shafts ok all but 2 wer flue.
INSP - Framing/Rough-in12/18/199712/18/199712/18/1997PPART
DetailsJim Storey
12/18/97 301 - 2 hr celling work in progess.
INSP - Conference8/18/19978/18/19978/18/1997 FAIL
DetailsJim Storey
/ / 301 - meet with special insp. and decused the out standing reports recieved. jan welsh w/ staply engeering, special insp. and myself to mee site as soon as fix for all isues is perposed. pending
INSP - Foundation7/3/19977/3/19977/3/1997PPART
DetailsJim Storey
07/03/97 301 - pouring at 11:30placed with special insp. pending report.
INSP - Framing/Rough-in6/30/19977/1/19977/1/1997ACANC
DetailsJim Storey
07/01/97 301 - drain thumps???? He will call you public works insp.
INSP - Foundation6/30/19976/30/19976/30/1997PPART
DetailsJim Storey
06/30/97 301 - pouring at 2 o'clock covered by special insp. pewnding report
INSP - Footings6/27/19976/27/19976/27/1997PPART
DetailsJim Storey
06/27/97 301 - REBAR EARLY PM POURING AT 2 P.M. FRMS-OK FORMS-REBAR covered by special insp report pending.