Permanent Occupancy | | 4/3/1998 | 4/3/1998 | | DONE |
|
|
|
|
INSP - Final | 4/1/1998 | 4/1/1998 | 4/1/1998 | | PASS |
Joe Tawney
|
|
|
/ / 406 - REINSP OK FOR PERM OCC
|
INSP - Final | 3/31/1998 | 4/1/1998 | 4/1/1998 | P | PASS |
|
|
|
04/01/98 338 - signed the occ req card fior the final occ . calle d cont
|
INSP-Alarm Testing | 3/17/1998 | 3/19/1998 | 3/19/1998 | A | PART |
Joe Tawney
|
|
|
03/19/98 406 - Don Walker - ###-#### - he would like for you to be there to do the alarm testing (before the box ofc. opens at 10:00) OK ON ALARM TEST NEED LETTER ON CHANGING H/S AND CENTR STAT CERTIFICATIO
|
INSP-Conference | 1/20/1998 | 1/20/1998 | 1/20/1998 | | PASS |
Joe Tawney
|
|
|
/ / 406 - TESTED NEW SPEAKER/STROBE OK ON DB LEVEL MUST RETAIN SAME CA
|
INSP - Final | 1/8/1998 | 1/8/1998 | 1/8/1998 | | FAIL |
Joe Tawney
|
|
|
/ / 406 - REINSP FOR PERM OCC FAIL VOICE EVAC DB TOOLOW OCC LOAD SIGNS
|
INSP - Temporary occupancy | 12/18/1997 | 12/18/1997 | 12/18/1997 | P | PASS |
|
|
|
12/18/97 338 - signed temp col of this card other agencies made ok
|
INSP - Final | 12/17/1997 | 12/17/1997 | 12/17/1997 | | PASS |
Joe Tawney
|
|
|
/ / 406 - FINAL OK FOR TEMP OCC AND ASSEMBLY PERMIT
|
INSP - Final | 12/16/1997 | 12/16/1997 | 12/16/1997 | | PART |
Joe Tawney
|
|
|
/ / 406 - ALARM FINAL PARTIAL OK NEED 5 MIN BAT TEST EMERG GEN TEST EL
|
INSP-Sprinkler Rough-in/Hydro | 12/10/1997 | 12/12/1997 | 12/12/1997 | A | PART |
Rick Jackson
|
|
|
12/12/97 409 - after 10:00 she will call completed hydro - pass. will do the flow test on Tuesday with fire alar testing.
|
INSP - Conference | 12/5/1997 | 12/5/1997 | 12/5/1997 | | PART |
|
|
|
/ / 338 - misc corrections 2 hrs
|
INSP-Conference | 12/4/1997 | 12/4/1997 | 12/4/1997 | | PASS |
Joe Tawney
|
|
|
/ / 406 - CHECKED FIRE EXT LOCATIONS AND FOUND LOCATIONS TO BE ACCEPTA
|
INSP-Conference | 12/2/1997 | 12/2/1997 | 12/2/1997 | | PASS |
Joe Tawney
|
|
|
/ / 406 - CONF ON ALARM SYSTEM AND SMOKE/FIRE DAMPERS REQ SUBMITTAL ON
|
INSP-Conference | 11/25/1997 | 11/25/1997 | 11/25/1997 | | PASS |
Joe Tawney
|
|
|
/ / 406 - INSPECTED SMOKE/FIRE DAMPERS NEED ACCESS OPENINGS AND INFO O
|
INSP-Sprinkler Rough-in/Hydro | 11/14/1997 | 11/17/1997 | 11/17/1997 | A | PART |
Joe Tawney
|
|
|
11/17/97 406 - THEATER OK ON ROUGH IN OF FRONT ENTRANCE AREA
|
INSP-Sprinkler Rough-in/Hydro | 10/30/1997 | 10/31/1997 | 10/31/1997 | A | PART |
Joe Tawney
|
|
|
10/31/97 406 - OK ON SPKLR ROUGH IN ON WEST SIDE LOWER LEVEL & LOWER CEN
|
INSP-Conference | 10/30/1997 | 10/30/1997 | 10/30/1997 | | PASS |
Joe Tawney
|
|
|
/ / 406 - PRE FINAL CONFERENCE WITH ALL INSPECTORS
|
INSP-Conference | 10/23/1997 | 10/23/1997 | 10/23/1997 | | PASS |
Joe Tawney
|
|
|
/ / 406 - CONF WITH HARRY & ANELL ABOUT FIRE EXT PLACEMENT IN THEATRE
|
INSP-Sprinkler Rough-in/Hydro | 10/14/1997 | 10/15/1997 | 10/15/1997 | A | PART |
Joe Tawney
|
|
|
10/15/97 406 - OK ON ROUGH IN FOR UPSTAIRS AREA AND EAST SIDE DOWNSTAIRS
|
INSP-Sprinkler Rough-in/Hydro | 9/30/1997 | 9/30/1997 | 9/30/1997 | P | FAIL |
Joe Tawney
|
|
|
09/30/97 406 - EDWARDS CINEMA spklr rough in fail SWAY BRACING HANGERS & STRAPS RELOCATE MAINS
|
INSP-Sprinkler Rough-in/Hydro | 9/24/1997 | 9/25/1997 | 9/25/1997 | A | CANC |
Rick Jackson
|
|
|
nobody on-site knew why we were requested
|
INSP - Conference | 9/22/1997 | 9/22/1997 | 9/22/1997 | P | PASS |
Tom Arcoraci
|
|
|
|
INSP-Supply line flush | 9/15/1997 | 9/15/1997 | 9/15/1997 | | PART |
Joe Tawney
|
|
|
/ / 406 - OK ON UNDERGROUND FLUSH
|
INSP-Sprinkler Rough-in/Hydro | 9/11/1997 | 9/12/1997 | 9/12/1997 | A | NR |
Joe Tawney
|
|
|
09/12/97 406 - underground flush NOT READY RESCH
|
INSP - Framing/Rough-in | 8/26/1997 | 8/27/1997 | 8/28/1997 | A | PART |
|
|
|
08/28/97 338 - WALKED TH SITE WITH RANDY, GOOD INSP. ONLY 40 PERSONS OR QUESTIONS ABOUT THE ELEVATOR SHAFT RE SETTING 1-HOUR 15 MIN
|
INSP - Framing/Rough-in | 8/18/1997 | 8/18/1997 | 8/18/1997 | | PASS |
|
|
|
08/18/97 338 - partial made ok verbal requirement for the minimum lap fo metal studs. what is used on the south west corner appears to be un acceptable.
|
INSP - Framing/Rough-in | 8/18/1997 | 8/18/1997 | 8/18/1997 | | PASS |
|
|
|
08/18/97 338 - partial made ok verbal requirement for the minimum lap fo metal studs. what is used on the south west corner appears to be un acceptable.
|
INSP-Conference | 5/12/1997 | 5/12/1997 | 5/12/1997 | P | PASS |
Joe Tawney
|
|
|
05/12/97 406 - CONFERENCE 2:00 PM DISCUSSED FD PLAN REVIEW AND REQUIREMENT FOR ALARM SYSTEM SUBMITTAL
|