Permit Information
Permit NumberBLD97-01808
StatusFinaled
Name JIM WOOD
Site Address 7736 W FAIRVIEW AVE
Project NamePOJO'S
Customer Number 
ePlanReviewNo
Description
*POJO'S* ADDITION OF 655 sq ft. to existing 21344 sq ft amusement building. And interior remodel to kitchen area, including new type 1 hood system and one-hour rated shaft. Adding additional area and seating to dinning area. Adding a carrosel to the ammusment area. Adding new entry vestibule, upgrading fire alarm system. And expanding mechanical system to new areas, all new penetrations to one hour ceilings shall be fire & smoke dampered. NOTE: This building is fully fire sprinklered for area increase. Any alteration or relocation to existing fire sprinkler system is to be per NFPA#13 as regulated by the fire department. DR#29-97 PC#383-97(RMH)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Occupancy 5/20/19985/20/1998 DONE
Details
INSP - Final5/18/19985/19/19985/19/1998PPASS
DetailsJim Sly
05/19/98 316 - OK for perm OCC.
INSP-Final Inspection5/13/19985/14/19985/14/1998PFAIL
DetailsJoe Tawney
05/14/98 406 - ###-#### REINP FAIL NEED INFO ON HOOD AND DUCT DETECTOR
INSP - Framing/Rough-in2/4/19982/5/19982/5/1998APART
DetailsJim Sly
02/04/98 316 - framing for towers Ext. front....OK
INSP - Final1/9/19981/12/19981/12/1998AFAIL
DetailsJim Sly
01/09/98 316 - C/N...Need required signatures..
INSP - Final1/12/19981/12/19981/12/1998 PASS
DetailsJim Sly
/ / 316 - Temp Occ.
INSP-Final Inspection1/9/19981/12/19981/12/1998APASS
DetailsJoe Tawney
01/12/98 406 - PoJo's Rod Hunt ###-#### REINSP OK FOR TEMP OCC SPKLR IN COOLER DUCT DET DOOR HDWRE HOOD CURBS
INSP - Final1/9/19981/9/19981/9/1998PNR
DetailsJim Sly
01/09/98 316 - Cancelled by owner....
INSP-Conference1/7/19981/7/19981/7/1998PPASS
DetailsJoe Tawney
/ / 406 - CONF ON CONNECTING COOK HOOD EXT SYSTEM TO ALARM SYSTEM
INSP - Final1/6/19981/6/19981/6/1998 FAIL
DetailsJoe Tawney
/ / 406 - ALARM SYSTEM TEST FAIL NO APPR SUB ON SITE DUCT DET & FIRE D
INSP - Final1/6/19981/6/19981/6/1998 FAIL
DetailsJoe Tawney
/ / 406 - ALARM SYSTEM TEST FAIL NO APPR SUB ON SITE DUCT DET & FIRE D
INSP - Final12/30/19971/6/19981/6/1998ANR
DetailsJim Sly
01/05/98 316 - Not Ready.
INSP - Framing/Rough-in12/18/199712/19/199712/19/1997APART
DetailsJim Sly
12/18/97 316 - pojo column pads S.W Addition...OK pending special insp a
INSP - Framing/Rough-in12/12/199712/15/199712/15/1997APART
DetailsJim Sly
12/12/97 316 - Framing of East addition OK
INSP - Framing/Rough-in12/11/199712/12/199712/12/1997AFAIL
DetailsJim Sly
12/11/97 316 - C/N..Arch to supply detail for light penitrations in 1hr
INSP-Final Inspection12/11/199712/12/199712/12/1997APART
DetailsRick Jackson
12/12/97 409 - rough in of new dining addition okay
INSP - Framing/Rough-in12/2/199712/2/199712/2/1997PNR
DetailsTom Arcoraci
POJO'S no elec inspec will recall
INSP - Miscellaneous12/1/199712/1/199712/1/1997PPASS
DetailsJim Sly
12/01/97 316 - pojo's fire shaft For Class A hood OK
INSP - Conference11/6/199711/7/199711/7/1997APASS
DetailsJim Sly
11/06/97 316 - Discussed issues on type 5 1hr bld....
INSP - Framing/Rough-in11/7/199711/7/199711/7/1997PPASS
DetailsJim Sly
11/07/97 316 - POJO'S OK to Cover South bay addition only.
INSP - Framing/Rough-in10/27/199710/27/199710/27/1997PPART
DetailsJim Sly
10/27/97 316 - Partial insp only..Kitch ceiling and firdowns OK only...
INSP-Sprinkler Rough-in/Hydro10/21/199710/22/199710/22/1997APART
DetailsJoe Tawney
10/22/97 406 - POJO'S OK ON SPKLR ROUGH IN FOR KITCHEN AREA
INSP - Framing/Rough-in10/20/199710/21/199710/21/1997AFAIL
DetailsJim Sly
10/20/97 316 - Arch to submit firestop assemb for 1hr rated constr....
INSP - Wall cover10/14/199710/14/199710/14/1997PPART
DetailsJim Sly
10/14/97 316 - STEM WALL OK pending special inspection and approval...
INSP - Footings10/13/199710/13/199710/13/1997PPART
DetailsJim Sly
10/13/97 316 - OK pending spec insp and approval...
INSP - Foundation10/6/199710/7/199710/7/1997APART
DetailsJim Sly
10/07/97 316 - REBAR FOR STEM WALL East side OK pending special insp app
INSP - Footings10/3/199710/6/199710/6/1997APART
DetailsJim Sly
10/06/97 316 - Footings East Wall OK pending special inspection and appr
INSP - Footings10/1/199710/1/199710/1/1997PPART
DetailsJim Sly
10/01/97 316 - STEMWALL At Carousel..OK pending spec insp and approval.
INSP - Footings9/29/19979/29/19979/29/1997PPART
DetailsJim Sly
09/29/97 316 - POJO'S Special inspection Req...Foot carousell area OK pe