INSP - Final | 5/24/1999 | 5/25/1999 | 5/25/1999 | A | PASS |
Jim Storey
|
|
|
05/25/99 301 - Anniversary Inn, final reinspect
|
Permanent Occupancy | | 5/24/1999 | 5/24/1999 | | DONE |
|
|
|
|
INSP - Final | 2/11/1999 | 2/11/1999 | 2/12/1999 | P | PART |
Jim Storey
|
|
|
02/11/99 301 - pending p/z ok and bond release.
|
INSP-Final Inspection | 2/10/1999 | 2/11/1999 | 2/11/1999 | | PASS |
Jim Storey
|
|
|
02/11/99 301 - final ok on bldg. side pending p/z sign off.
|
INSP-Final Inspection | 2/10/1999 | 2/11/1999 | 2/11/1999 | A | PASS |
Rick Jackson
|
|
|
dennis ###-####- occ approved
|
INSP-Final Inspection | 2/4/1999 | 2/4/1999 | 2/4/1999 | P | |
Mike Kinnear
|
|
|
Ron, ###-#### or Dennis (gen. mgr.)
|
INSP-Final Inspection | 1/28/1999 | 1/28/1999 | 1/28/1999 | P | PART |
Rick Jackson
|
|
|
RON ###-#### SPOKE WITH BILL ALEXANDER still need sidewall sprinkler for spare head box
|
INSP - Final | 1/13/1999 | 1/13/1999 | 1/13/1999 | | FAIL |
Jim Storey
|
|
|
/ / 301 - FIRE RE-SUBMITAL LACK OF INFO.ENGINEER TO VERRIFY AND RESUBM
|
INSP - Final | 12/10/1998 | 12/10/1998 | 12/12/1998 | P | PART |
Jim Storey
|
|
|
12/11/98 301 - signed off by george slane
|
INSP-Final Inspection | 12/10/1998 | 12/10/1998 | 12/10/1998 | P | FAIL |
Mike Kinnear
|
|
|
Fire sprinkler calculations and sprinkler piping installed did not match what was submitted as an asbuilt design for appoval. Instructed with notification to redesign, recalculate, resubmit.
|
INSP - Final | 12/9/1998 | 12/9/1998 | 12/9/1998 | P | PART |
Jim Storey
|
|
|
12/09/98 301 - roof draft stops and access ok corridor fire stopping ok
|
INSP - Final | 12/8/1998 | 12/9/1998 | 12/9/1998 | A | PART |
Jim Storey
|
|
|
roof draft stops ok fire stopping ok in corridors.
|
INSP-Final Inspection | 12/9/1998 | 12/9/1998 | 12/9/1998 | P | FAIL |
Rick Jackson
|
|
|
requested by alarm company reinspect of alarms - okay. several sprinkler issues left. emergency lights okay.
|
INSP - Wall cover | 12/8/1998 | 12/8/1998 | 12/8/1998 | P | PASS |
Jim Storey
|
|
|
12/08/98 301 - SCLG-OK SUSPENDED CEILING
|
INSP-Sprinkler Rough-in/Hydro | 12/8/1998 | 12/8/1998 | 12/8/1998 | P | PART |
Rick Jackson
|
|
|
checked heads to meet John Jensen's changes - okay
|
INSP - Framing/Rough-in | 12/7/1998 | 12/7/1998 | 12/8/1998 | P | PART |
Russ Owen
|
|
|
12/08/98 407 - ok to drop lids in hallway.
|
INSP-Alarm Testing | 12/7/1998 | 12/7/1998 | 12/7/1998 | A | FAIL |
Rick Jackson
|
|
|
all detectors not installed per plans; doors with hold opens not complete; two smokes and 1 strobe not working; NFPA 72 and plans; install detector in future guest room and room 32 - c/n issued
|
INSP-Sprinkler Rough-in/Hydro | 12/7/1998 | 12/7/1998 | 12/7/1998 | A | PASS |
Rick Jackson
|
|
|
hydro only - pass
|
INSP-Final Inspection | 12/2/1998 | 12/4/1998 | 12/4/1998 | A | FAIL |
Rick Jackson
|
|
|
###-#### RALPH alarms not complete; address; fire marshall plans; test alarms; door holders/closures not on; etc, etc
|
INSP - Framing/Rough-in | 12/3/1998 | 12/3/1998 | 12/3/1998 | P | |
Jim Storey
|
|
|
mike ###-#### per jim storey for 12-03-98 pm
|
INSP-Conference | 12/3/1998 | 12/3/1998 | 12/3/1998 | P | FAIL |
Rick Jackson
|
|
|
alarms not complete; state approved sprinkler plans,
|
INSP - Wall cover | 11/18/1998 | 11/19/1998 | 11/19/1998 | A | FAIL |
Jim Storey
|
|
|
11/19/98 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
|
INSP-Conference | 11/13/1998 | 11/13/1998 | 11/13/1998 | P | PART |
Rick Jackson
|
|
|
jensen,pe is to come up with plan to increase sprinkler density within rooms having foam
|
INSP-Conference | 10/22/1998 | 10/22/1998 | 10/22/1998 | A | PART |
Rick Jackson
|
|
|
conference with George and architect about interior use of foam and spray on finishes. arc. to supply more data for approval
|
INSP-Conference | 10/19/1998 | 10/19/1998 | 10/19/1998 | P | PART |
Rick Jackson
|
|
|
issued and reviewed c/n with contractor about sprinkler problems
|
INSP-Sprinkler Rough-in/Hydro | 10/15/1998 | 10/15/1998 | 10/15/1998 | P | FAIL |
Rick Jackson
|
|
|
continued sprinkler rough-in, c/n forthcoming
|
INSP-Sprinkler Rough-in/Hydro | 10/14/1998 | 10/14/1998 | 10/14/1998 | A | FAIL |
Rick Jackson
|
|
|
c/n to be issued for numerous sprinkler problems
|
INSP-Sprinkler Rough-in/Hydro | 10/13/1998 | 10/13/1998 | 10/13/1998 | P | FAIL |
Rick Jackson
|
|
|
bathroom corridor not sprinklered; linen/mop closet not sprinklered; overspacing with sidewalls
|
INSP - Framing/Rough-in | 9/28/1998 | 9/29/1998 | 9/29/1998 | P | PASS |
Jim Storey
|
|
|
09/29/98 301 - mike ###-#### GWB -OK SHEETROCK NAILING ì
|
INSP - Wall cover | 9/28/1998 | 9/28/1998 | 9/28/1998 | | PASS |
Jim Storey
|
|
|
/ / 301 - GEN -GENERAL INSPECTION fire stopping and gaurd raillings stair height o
|
INSP - Energy code compliance | 9/21/1998 | 9/22/1998 | 9/22/1998 | A | CANC |
Russ Owen
|
|
|
09/22/98 407 - trans to 301.
|
INSP - Wall cover | 8/19/1998 | 8/19/1998 | 8/19/1998 | | PASS |
Jim Storey
|
|
|
/ / 301 - reviewed w/arch fire damper access and drop ceillings in wat pending submitals. approved rated shaft assembly for bolier flue. need submital for change of round flue to oval for mech review to meet cleara of flue in shaft.
|
INSP - Energy code compliance | 8/13/1998 | 8/14/1998 | 8/14/1998 | A | PASS |
Jim Storey
|
|
|
08/14/98 301 - MIKE ###-#### INSL-OK INSULATION ì
|
INSP - Framing/Rough-in | 8/13/1998 | 8/14/1998 | 8/14/1998 | A | PASS |
Jim Storey
|
|
|
08/14/98 301 - WALL COVER MIKE ###-#### GWB -OK SHEETROCK NAILING
|
INSP - Framing/Rough-in | 8/5/1998 | 8/6/1998 | 8/6/1998 | P | PASS |
Jim Storey
|
|
|
08/06/98 301 - FRAMING 3RD STORY MIKE ###-#### FRAM-OK FRAMING
|
INSP - Framing/Rough-in | 7/24/1998 | 7/27/1998 | 7/27/1998 | A | FAIL |
Jim Storey
|
|
|
07/27/98 301 - Scheduled by Hello!. Contact phone is [8901616]. CORR-CORREC-CALL FOR REINSP WHEN COMPLETED ok to insulate exterior walls floor .
|
INSP - Energy code compliance | 7/21/1998 | 7/22/1998 | 7/22/1998 | P | PART |
Jim Storey
|
|
|
07/22/98 301 - Scheduled by Hello!. Contact phone is [3319055]. FRAM-OK FRAMING ok and insulation ok for 2nd floor .
|
INSP - Energy code compliance | 7/17/1998 | 7/20/1998 | 7/20/1998 | A | PASS |
Jim Storey
|
|
|
07/20/98 301 - Scheduled by Hello!. INSL-OK INSULATION
|
INSP - Energy code compliance | 7/17/1998 | 7/17/1998 | 7/17/1998 | | PART |
Jim Storey
|
|
|
07/16/98 301 - ###-#### bill CORR-CORREC-CALL FOR REINSP WHEN COMPLETED ok to start lids ì
|
INSP - Wall cover | 7/6/1998 | 7/7/1998 | 7/7/1998 | A | PART |
Jim Storey
|
|
|
07/07/98 301 - 2nd floor ok for insulation/ first floor ok to hang ceill lacking r/c chanel reinsp required.
|
INSP - Framing/Rough-in | 7/1/1998 | 7/2/1998 | 7/2/1998 | A | PART |
|
|
|
07/02/98 333 - basement ok to insulate
|
INSP - Energy code compliance | 6/16/1998 | 6/17/1998 | 6/18/1998 | A | FAIL |
Jim Storey
|
|
|
06/17/98 301 - n/r conf only.
|
INSP-Sprinkler Rough-in/Hydro | 6/15/1998 | 6/15/1998 | 6/15/1998 | P | PART |
Rick Jackson
|
|
|
riser and all areas not complete. not approved for cover.
|
INSP - Framing/Rough-in | 5/12/1998 | 5/12/1998 | 5/12/1998 | P | PART |
Jim Storey
|
|
|
05/12/98 301 - SHRW-OK SHEARWALL NAILING on all but wall framing north f
|
INSP-Conference | 4/9/1998 | 4/9/1998 | 4/9/1998 | A | PART |
Rick Jackson
|
|
|
pre-con with Jim S. and contractor/subs. requested alarm submittals - contract for alarms not let as of today
|
INSP - Framing/Rough-in | 4/3/1998 | 4/3/1998 | 4/3/1998 | A | PART |
Jim Storey
|
|
|
conf. set up preconst meeting for 4/9/98
|
INSP-Supply line flush | 3/30/1998 | 3/30/1998 | 3/30/1998 | A | PASS |
Rick Jackson
|
|
|
underground hydro and flush okay
|
INSP - Foundation | 3/23/1998 | 3/23/1998 | 3/23/1998 | P | PASS |
Jim Storey
|
|
|
03/23/98 301 - Scheduled by Hello!. wall ok
|
INSP - Foundation | 3/19/1998 | 3/19/1998 | 3/20/1998 | P | PASS |
Jim Storey
|
|
|
03/20/98 301 - FRMS-OK FORMS-REBAR
|
INSP - Foundation | 3/17/1998 | 3/18/1998 | 3/18/1998 | P | PASS |
Jim Storey
|
|
|
Scheduled by Hello!. Contact phone is [8901616]. slab and thickened footings ok
|
INSP - Foundation | 3/9/1998 | 3/9/1998 | 3/9/1998 | P | PASS |
Jim Storey
|
|
|
03/09/98 301 - Scheduled by Hello!. Contact phone is [8901616]. FDN -OK FOUNDATION
|
INSP - Foundation | 3/5/1998 | 3/5/1998 | 3/5/1998 | P | PASS |
Jim Storey
|
|
|
03/05/98 301 - bill ###-#### FRMS-OK FORMS-REBAR EAST AND NORTH WALL LINES ì
|
INSP - Foundation | 2/26/1998 | 2/27/1998 | 2/27/1998 | P | PASS |
Jim Storey
|
|
|
02/27/98 301 - FOR STEEL--MIKE ###-####--ANNIVERSARY INN FRMS-OK FORMS-REBAR
|
INSP - Foundation | 2/23/1998 | 2/23/1998 | 2/23/1998 | P | PASS |
Jim Storey
|
|
|
02/23/98 301 - ###-#### MIKE FRMS-OK FORMS-REBAR ì
|