Permit Information
Permit NumberBLD97-02083
StatusFinaled
Name ANNIVERSARY INN
Site Address 1575 S LUSK ST
Project NameANNIVERSARY INN
Customer Number 
ePlanReviewNo
Description
ANNIVERSARY INN * TO CONSTRUCT A NEW 20,396 SQ FT., 41 UNIT MOTEL, 32 ROOMS WILL BE COMPLETED AT THIS TIME. CONSTRUCTION TO BE A TWO STORY, WITH A MEZZAINNES ON THE SECOND FLOOR AND A BASEMENT, WOOD FRAMED TYPE V-ONE-HOUR CONSTRUCTION, FULLY FIRE SPRINKLERED 13-R SYSTEM. THE INSTALLATION OF THE FIRE SPRINKLER SYSTEM IS PER SECTION 904.2.8 AND CAN NOT BE USED FOR ANY CODE REDUCTIONS. THE FIRST FLOOR IS APPROXIMATELY 9161 SQ.FT. THE SECOND FLOOR IS 10216 SQ.FT. WHICH INCLUDES THE MEZZANNINES, THE BASEMENT IS APPROXIMATELY 9720 SQ.FT. THIS PERMIT TO INCLUDE RELATED ON SITE WORK. MJP (PC#469-97) DR-97-97 CU-41-97
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP - Final5/24/19995/25/19995/25/1999APASS
DetailsJim Storey
05/25/99 301 - Anniversary Inn, final reinspect
Permanent Occupancy 5/24/19995/24/1999 DONE
Details
INSP - Final2/11/19992/11/19992/12/1999PPART
DetailsJim Storey
02/11/99 301 - pending p/z ok and bond release.
INSP-Final Inspection2/10/19992/11/19992/11/1999 PASS
DetailsJim Storey
02/11/99 301 - final ok on bldg. side pending p/z sign off.
INSP-Final Inspection2/10/19992/11/19992/11/1999APASS
DetailsRick Jackson
dennis ###-####- occ approved
INSP-Final Inspection2/4/19992/4/19992/4/1999P
DetailsMike Kinnear
Ron, ###-#### or Dennis (gen. mgr.)
INSP-Final Inspection1/28/19991/28/19991/28/1999PPART
DetailsRick Jackson
RON ###-#### SPOKE WITH BILL ALEXANDER still need sidewall sprinkler for spare head box
INSP - Final1/13/19991/13/19991/13/1999 FAIL
DetailsJim Storey
/ / 301 - FIRE RE-SUBMITAL LACK OF INFO.ENGINEER TO VERRIFY AND RESUBM
INSP - Final12/10/199812/10/199812/12/1998PPART
DetailsJim Storey
12/11/98 301 - signed off by george slane
INSP-Final Inspection12/10/199812/10/199812/10/1998PFAIL
DetailsMike Kinnear
Fire sprinkler calculations and sprinkler piping installed did not match what was submitted as an asbuilt design for appoval. Instructed with notification to redesign, recalculate, resubmit.
INSP - Final12/9/199812/9/199812/9/1998PPART
DetailsJim Storey
12/09/98 301 - roof draft stops and access ok corridor fire stopping ok
INSP - Final12/8/199812/9/199812/9/1998APART
DetailsJim Storey
roof draft stops ok fire stopping ok in corridors.
INSP-Final Inspection12/9/199812/9/199812/9/1998PFAIL
DetailsRick Jackson
requested by alarm company reinspect of alarms - okay. several sprinkler issues left. emergency lights okay.
INSP - Wall cover12/8/199812/8/199812/8/1998PPASS
DetailsJim Storey
12/08/98 301 - SCLG-OK SUSPENDED CEILING
INSP-Sprinkler Rough-in/Hydro12/8/199812/8/199812/8/1998PPART
DetailsRick Jackson
checked heads to meet John Jensen's changes - okay
INSP - Framing/Rough-in12/7/199812/7/199812/8/1998PPART
DetailsRuss Owen
12/08/98 407 - ok to drop lids in hallway.
INSP-Alarm Testing12/7/199812/7/199812/7/1998AFAIL
DetailsRick Jackson
all detectors not installed per plans; doors with hold opens not complete; two smokes and 1 strobe not working; NFPA 72 and plans; install detector in future guest room and room 32 - c/n issued
INSP-Sprinkler Rough-in/Hydro12/7/199812/7/199812/7/1998APASS
DetailsRick Jackson
hydro only - pass
INSP-Final Inspection12/2/199812/4/199812/4/1998AFAIL
DetailsRick Jackson
###-#### RALPH alarms not complete; address; fire marshall plans; test alarms; door holders/closures not on; etc, etc
INSP - Framing/Rough-in12/3/199812/3/199812/3/1998P
DetailsJim Storey
mike ###-#### per jim storey for 12-03-98 pm
INSP-Conference12/3/199812/3/199812/3/1998PFAIL
DetailsRick Jackson
alarms not complete; state approved sprinkler plans,
INSP - Wall cover11/18/199811/19/199811/19/1998AFAIL
DetailsJim Storey
11/19/98 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP-Conference11/13/199811/13/199811/13/1998PPART
DetailsRick Jackson
jensen,pe is to come up with plan to increase sprinkler density within rooms having foam
INSP-Conference10/22/199810/22/199810/22/1998APART
DetailsRick Jackson
conference with George and architect about interior use of foam and spray on finishes. arc. to supply more data for approval
INSP-Conference10/19/199810/19/199810/19/1998PPART
DetailsRick Jackson
issued and reviewed c/n with contractor about sprinkler problems
INSP-Sprinkler Rough-in/Hydro10/15/199810/15/199810/15/1998PFAIL
DetailsRick Jackson
continued sprinkler rough-in, c/n forthcoming
INSP-Sprinkler Rough-in/Hydro10/14/199810/14/199810/14/1998AFAIL
DetailsRick Jackson
c/n to be issued for numerous sprinkler problems
INSP-Sprinkler Rough-in/Hydro10/13/199810/13/199810/13/1998PFAIL
DetailsRick Jackson
bathroom corridor not sprinklered; linen/mop closet not sprinklered; overspacing with sidewalls
INSP - Framing/Rough-in9/28/19989/29/19989/29/1998PPASS
DetailsJim Storey
09/29/98 301 - mike ###-#### GWB -OK SHEETROCK NAILING ì
INSP - Wall cover9/28/19989/28/19989/28/1998 PASS
DetailsJim Storey
/ / 301 - GEN -GENERAL INSPECTION fire stopping and gaurd raillings stair height o
INSP - Energy code compliance9/21/19989/22/19989/22/1998ACANC
DetailsRuss Owen
09/22/98 407 - trans to 301.
INSP - Wall cover8/19/19988/19/19988/19/1998 PASS
DetailsJim Storey
/ / 301 - reviewed w/arch fire damper access and drop ceillings in wat pending submitals. approved rated shaft assembly for bolier flue. need submital for change of round flue to oval for mech review to meet cleara of flue in shaft.
INSP - Energy code compliance8/13/19988/14/19988/14/1998APASS
DetailsJim Storey
08/14/98 301 - MIKE ###-#### INSL-OK INSULATION ì
INSP - Framing/Rough-in8/13/19988/14/19988/14/1998APASS
DetailsJim Storey
08/14/98 301 - WALL COVER MIKE ###-#### GWB -OK SHEETROCK NAILING
INSP - Framing/Rough-in8/5/19988/6/19988/6/1998PPASS
DetailsJim Storey
08/06/98 301 - FRAMING 3RD STORY MIKE ###-#### FRAM-OK FRAMING
INSP - Framing/Rough-in7/24/19987/27/19987/27/1998AFAIL
DetailsJim Storey
07/27/98 301 - Scheduled by Hello!. Contact phone is [8901616]. CORR-CORREC-CALL FOR REINSP WHEN COMPLETED ok to insulate exterior walls floor .
INSP - Energy code compliance7/21/19987/22/19987/22/1998PPART
DetailsJim Storey
07/22/98 301 - Scheduled by Hello!. Contact phone is [3319055]. FRAM-OK FRAMING ok and insulation ok for 2nd floor .
INSP - Energy code compliance7/17/19987/20/19987/20/1998APASS
DetailsJim Storey
07/20/98 301 - Scheduled by Hello!. INSL-OK INSULATION
INSP - Energy code compliance7/17/19987/17/19987/17/1998 PART
DetailsJim Storey
07/16/98 301 - ###-#### bill CORR-CORREC-CALL FOR REINSP WHEN COMPLETED ok to start lids ì
INSP - Wall cover7/6/19987/7/19987/7/1998APART
DetailsJim Storey
07/07/98 301 - 2nd floor ok for insulation/ first floor ok to hang ceill lacking r/c chanel reinsp required.
INSP - Framing/Rough-in7/1/19987/2/19987/2/1998APART
Details
07/02/98 333 - basement ok to insulate
INSP - Energy code compliance6/16/19986/17/19986/18/1998AFAIL
DetailsJim Storey
06/17/98 301 - n/r conf only.
INSP-Sprinkler Rough-in/Hydro6/15/19986/15/19986/15/1998PPART
DetailsRick Jackson
riser and all areas not complete. not approved for cover.
INSP - Framing/Rough-in5/12/19985/12/19985/12/1998PPART
DetailsJim Storey
05/12/98 301 - SHRW-OK SHEARWALL NAILING on all but wall framing north f
INSP-Conference4/9/19984/9/19984/9/1998APART
DetailsRick Jackson
pre-con with Jim S. and contractor/subs. requested alarm submittals - contract for alarms not let as of today
INSP - Framing/Rough-in4/3/19984/3/19984/3/1998APART
DetailsJim Storey
conf. set up preconst meeting for 4/9/98
INSP-Supply line flush3/30/19983/30/19983/30/1998APASS
DetailsRick Jackson
underground hydro and flush okay
INSP - Foundation3/23/19983/23/19983/23/1998PPASS
DetailsJim Storey
03/23/98 301 - Scheduled by Hello!. wall ok
INSP - Foundation3/19/19983/19/19983/20/1998PPASS
DetailsJim Storey
03/20/98 301 - FRMS-OK FORMS-REBAR
INSP - Foundation3/17/19983/18/19983/18/1998PPASS
DetailsJim Storey
Scheduled by Hello!. Contact phone is [8901616]. slab and thickened footings ok
INSP - Foundation3/9/19983/9/19983/9/1998PPASS
DetailsJim Storey
03/09/98 301 - Scheduled by Hello!. Contact phone is [8901616]. FDN -OK FOUNDATION
INSP - Foundation3/5/19983/5/19983/5/1998PPASS
DetailsJim Storey
03/05/98 301 - bill ###-#### FRMS-OK FORMS-REBAR EAST AND NORTH WALL LINES ì
INSP - Foundation2/26/19982/27/19982/27/1998PPASS
DetailsJim Storey
02/27/98 301 - FOR STEEL--MIKE ###-####--ANNIVERSARY INN FRMS-OK FORMS-REBAR
INSP - Foundation2/23/19982/23/19982/23/1998PPASS
DetailsJim Storey
02/23/98 301 - ###-#### MIKE FRMS-OK FORMS-REBAR ì