INSP - Final | 5/26/1998 | 5/27/1998 | 5/27/1998 | P | PASS |
Jim Storey
|
|
|
05/27/98 301 - FNL -OK FINAL
|
Permanent Occupancy | | 5/27/1998 | 5/27/1998 | | DONE |
|
|
|
|
INSP - Final | 3/19/1998 | 3/20/1998 | 3/20/1998 | P | PASS |
Jim Storey
|
|
|
03/20/98 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED temp ok for al
|
INSP-Final Inspection | 3/19/1998 | 3/20/1998 | 3/20/1998 | A | PASS |
Rick Jackson
|
|
|
301 IS GOING OUT ALSO IN THE PM PAT-###-#### all items corrected. occ approved
|
INSP - Final | 2/27/1998 | 2/27/1998 | 2/27/1998 | P | PART |
Jim Storey
|
|
|
02/27/98 301 - ###-#### pat FNL -OK FINAL OF THE OFFICE AREA FIRST FLOOR ONLY. NO OCCUPANCY OF THE S STORAGE AREA ABOVE THE OFFICE AND WAREHOUSE IS TO BE ALLOWED. ALL WORK P SCOPE OF PERMIT IS TO BE COMPLETED FOR PERMINT SIGN OFF WITH IN MAX. 90 TEMP.OCC GRACE
|
INSP-Final Inspection | 2/27/1998 | 2/27/1998 | 2/27/1998 | P | PART |
Rick Jackson
|
|
|
requested by steed. temp occ approved for office only. sprinklers for racking not complete. hydro and monitoring tests okay.
|
INSP-Conference | 2/27/1998 | 2/18/1998 | 2/27/1998 | | PASS |
|
|
|
DSM met with dave kadanko & based on the ongoing discussions & test in the code world surrounding smoke curtains, vents, & spk as they interreelate for high piled & rack storage, dsm agreed to approve kadanko request for draft curtain area of 3300 sqft Provided they use ELO sprinklers.
|
INSP - Framing/Rough-in | 2/25/1998 | 2/26/1998 | 2/26/1998 | A | CANC |
Russ Owen
|
|
|
02/26/98 407 - trans to 301 nspection
|
INSP-Sprinkler Rough-in/Hydro | 2/25/1998 | 2/25/1998 | 2/25/1998 | P | PART |
Rick Jackson
|
|
|
rough-in of office area - okay. seismic in warehouse not complete. mezzanine not sprinklered yet, small part of warehouse not complete. still needs hydro and monitoring.
|
INSP - Framing/Rough-in | 2/20/1998 | 2/23/1998 | 2/24/1998 | P | NR |
Jim Storey
|
|
|
02/23/98 301 - ###-#### state liquor recall
|
INSP-Conference | 2/11/1998 | 2/11/1998 | 2/11/1998 | P | PART |
Rick Jackson
|
|
|
discussed curtain board design/area coverage. areas under boards are over 3,000 sq ft. steed to contact hummel about problem.
|
INSP - Framing/Rough-in | 1/16/1998 | 1/20/1998 | 1/21/1998 | A | NH |
Russ Owen
|
|
|
01/20/98 407 - could not find the contractor.called the number no answer they wanted.
|