INSP - Final | 12/19/1997 | 12/19/1997 | 12/19/1997 | | PASS |
Jim Storey
|
|
|
12/19/97 301 - Final FNL -OK FINAL
|
INSP - Final | 12/19/1997 | 12/19/1997 | 12/19/1997 | | PASS |
Jim Storey
|
|
|
12/19/97 301 - Final FNL -OK FINAL
|
INSP - Letter of compliance | 12/19/1997 | 12/19/1997 | 12/19/1997 | | PASS |
Jim Storey
|
|
|
/ / 301 - LCI-LETTER OF COMPLIANCE ISSUED 14208
|
INSP - Letter of compliance | 12/19/1997 | 12/19/1997 | 12/19/1997 | | PASS |
Jim Storey
|
|
|
/ / 301 - LCI-LETTER OF COMPLIANCE ISSUED 14208
|
INSP - Letter of compliance | 12/19/1997 | 12/19/1997 | 12/19/1997 | | PASS |
Jim Storey
|
|
|
/ / 301 - LCI-LETTER OF COMPLIANCE ISSUED 14208
|
INSP - Letter of compliance | 12/19/1997 | 12/19/1997 | 12/19/1997 | | PASS |
Jim Storey
|
|
|
/ / 301 - LCI-LETTER OF COMPLIANCE ISSUED 14208
|
INSP - Energy code compliance | 11/28/1997 | 11/28/1997 | 11/28/1997 | | PASS |
Jim Storey
|
|
|
/ / 301 - INSL-OK INSULATION-ENERGY CODE
|
INSP - Framing/Rough-in | 11/26/1997 | 11/26/1997 | 11/28/1997 | P | PASS |
Jim Storey
|
|
|
11/26/97 301 - Wanted an additional inspection if you don't pass him at FRAM-OK FRAMING
|
INSP - Framing/Rough-in | 11/25/1997 | 11/26/1997 | 11/26/1997 | P | PART |
Jim Storey
|
|
|
11/26/97 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED ok to insulate
|
INSP - Conference | 11/18/1997 | 11/18/1997 | 11/18/1997 | | FAIL |
|
|
|
Conference w/Foundation supplier.#1. Product is not approved by this jurisdiction,no ICBO or supporting analysis (info from Bob G.). #2. Contractor proceeded beyond early start permit(framing stage).#3 Product not installed per manufactures requirements. #4 Foundation is to be removed and replaced w/conventional wall.
|
INSP - Miscellaneous | 11/17/1997 | 11/17/1997 | 11/17/1997 | A | FAIL |
Jim Storey
|
|
|
11/17/97 301 - Place a swo on this project for unapproved material and i manufactures recomendations, #325. stop work posted...
|
INSP - Footings | 10/29/1997 | 10/29/1997 | 10/30/1997 | P | FAIL |
Jim Storey
|
|
|
10/29/97 301 - will you please check on the foundation between 2401 and that was poured w/o an inspection to see if the space between them are correct. no plan on site, p/l not able to find pins, fence is 5' from footing on side, early sta
|
INSP - Footings | 10/22/1997 | 10/22/1997 | 10/23/1997 | P | PART |
Jim Storey
|
|
|
10/22/97 301 - Early start - Hi rickshaw rider!! EAR-EARLY START POURED WITHOUT INSPECTION
|