INSP - Final | 9/14/1998 | 9/14/1998 | 9/14/1998 | | PASS |
Jim Storey
|
|
|
/ / 301 - FNL -OK FINAL
|
INSP-Final Inspection | 9/10/1998 | 9/10/1998 | 9/10/1998 | P | PASS |
Rick Jackson
|
|
|
occ approved
|
INSP-Final Inspection | 6/15/1998 | 6/15/1998 | 6/15/1998 | A | PART |
Rick Jackson
|
|
|
tested tampers for sprinkler - okay. knox box installed and duct detectors shut downs - okay. fire lanes painted on 6/16.
|
INSP - Final | 6/9/1998 | 6/10/1998 | 6/10/1998 | A | PART |
Jim Storey
|
|
|
06/10/98 301 - final ok pending fire insp. isues...
|
INSP-Final Inspection | 6/9/1998 | 6/9/1998 | 6/9/1998 | P | PART |
Rick Jackson
|
|
|
as per 409 2:30 TIME/TRACY ###-#### tampers retest, AHU shutdown, etc. c/n issued
|
INSP - Final | 5/21/1998 | 5/22/1998 | 5/26/1998 | P | NR |
Russ Owen
|
|
|
05/22/98 407 - not ready,need other inspections. plumbing,fire
|
INSP - Framing/Rough-in | 5/7/1998 | 5/7/1998 | 5/8/1998 | P | PART |
Russ Owen
|
|
|
05/07/98 407 - inside non-bearing walls ok. need stell joist lay out app
|
INSP-Sprinkler Rough-in/Hydro | 5/6/1998 | 5/6/1998 | 5/6/1998 | P | PART |
Rick Jackson
|
|
|
esfr sprinkler heads obstructed by ductwork
|
INSP - Foundation | 3/24/1998 | 3/24/1998 | 3/25/1998 | P | PART |
Russ Owen
|
|
|
03/24/98 407 - this foundation is required to have special inspector app to reports.
|
INSP - Foundation | 3/20/1998 | 3/23/1998 | 3/24/1998 | A | PART |
Russ Owen
|
|
|
03/23/98 407 - this job is under special inspection.Subject to the repor
|
INSP - Foundation | 3/23/1998 | 3/23/1998 | 3/23/1998 | P | PART |
|
|
|
03/23/98 333 - pending si reports
|
INSP - Foundation | 3/19/1998 | 3/19/1998 | 3/20/1998 | P | PART |
Russ Owen
|
|
|
03/19/98 407 - this requires special inspection,pending reports.
|
INSP - Foundation | 3/18/1998 | 3/18/1998 | 3/18/1998 | P | PART |
Russ Owen
|
|
|
03/18/98 407 - this requires special inspection subject to report.
|