INSP - Final | 9/11/1998 | 9/14/1998 | 9/14/1998 | A | PASS |
Jim Storey
|
|
|
09/14/98 301 - CHRIS ###-#### FNL -OK FINAL card w/contractor for city sign offs. ì
|
Permanent Occupancy | | 9/14/1998 | 9/14/1998 | | DONE |
|
|
|
|
INSP - Final | 9/10/1998 | 9/11/1998 | 9/11/1998 | A | CANC |
Wes Worcester
|
|
|
09/11/98 342 - chris ###-####
|
INSP-Final Inspection | 9/10/1998 | 9/10/1998 | 9/10/1998 | P | PASS |
Rick Jackson
|
|
|
chris occ approved
|
INSP-Sprinkler Rough-in/Hydro | 9/10/1998 | 9/10/1998 | 9/10/1998 | P | PASS |
Rick Jackson
|
|
|
CHRIS ###-#### COME AFTER 2:30 IF POSSIBLE sprinkler heads okay in new offices
|
INSP-Conference | 9/4/1998 | 9/8/1998 | 9/9/1998 | A | PART |
Russ Owen
|
|
|
09/09/98 407 - has corrections with some wall braces and draft curtins. also fire life safety items.
|
INSP-Conference | 9/4/1998 | 9/8/1998 | 9/8/1998 | A | PART |
Rick Jackson
|
|
|
conference chris ###-#### final requirements: sprinklers obstructed in offices; alarms not complete or tested
|
INSP - Framing/Rough-in | 7/8/1998 | 7/9/1998 | 7/9/1998 | A | PART |
Russ Owen
|
|
|
07/09/98 407 - Office space,Have corrections for the doors CABO/ANSI req vestibule pull side. ì
|
INSP - Framing/Rough-in | 6/18/1998 | 6/18/1998 | 6/18/1998 | P | PART |
Russ Owen
|
|
|
06/18/98 407 - Wanted to Know if they could occupy an office space in th this would need approval from Fire life safty and our division also poss others.
|