Permit Information
Permit NumberBLD98-01416
StatusFinaled
Name ALBERTSON' INC
Site Address 6560 S FEDERAL WAY
Project NameALBERTSONS 184
Customer Number 
ePlanReviewNo
Description
ALBERTSON'S FOOD CENTER #184 * TO CONSTRUCT A NEW 60,013 SQ.FT. RETAIL FOOD CENTER WITH DELI AND BAKERY. THIS IS A SINGLE STORY, CONCRETE MASONRY UNIT, FULLY FIRE SPRINKLERED, TYPE III ONE-HOUR, GROCERY STORE. THE MERCANTILE FLOOR AREA IS APPROXIMATELY 56,104 SQ.FT. 2,177 SQ.FT. IS FOR THE MECHANICAL MEZZANINE AND 1,732 SQ.FT IS FOR THE COVERED ENTRY AREA. THE INSTALLATION OF THE FIRE SPRINKLER SYSTEM IS BEING USED FOR ALLOWABLE AREA INCREASE. ALL CONSTRUCTION PER THE APPROVED PLANS, ATTACHED COMMENT LIST, CABO/ANSI A117.1 AND THE 1994 EDITION OF THE UBC. PERMIT TO INCLUDE FLAT WORK AROUND THE BUILDING ONLY. DR-19-97 MJP (PC#98-315)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP - Wall cover8/31/19998/31/19998/31/1999 PASS
DetailsJim Storey
archived intior finsh report to meet smoke/flame test
INSP - Final6/8/19996/8/19996/8/1999PPASS
DetailsJim Storey
06/08/99 301 - final ok
Permanent Occupancy 6/8/19996/8/1999 DONE
Details
INSP-Final Inspection6/7/19996/7/19996/7/1999AFAIL
DetailsRick Jackson
emergency tested - passed; need balance report for kitchen system; perm address
INSP-Alarm Testing6/3/19996/3/19996/3/1999PPART
DetailsRick Jackson
tested hood extinguishing system - okay; beed balance report
INSP - Framing/Rough-in5/21/19995/24/19995/24/1999AFAIL
DetailsJim Storey
05/24/99 301 - c/n isued
INSP - Framing/Rough-in5/18/19995/18/19995/18/1999 PASS
DetailsJim Storey
05/18/99 301 - ceilling ok
INSP-Final Inspection5/17/19995/17/19995/17/1999PFAIL
DetailsRick Jackson
###-#### TRACY//FINAL 1:00-1:30 PLEASE sprinkler alarms okay; tags and signs needed for sprinklers; alarms not complete; kicthen hood not complete; obstructions in sales floor; c/n issued
INSP - Framing/Rough-in5/5/19995/6/19995/6/1999AFAIL
DetailsJim Storey
05/06/99 301 - fire calk/ Mel ###-####
INSP-Conference5/3/19995/3/19995/3/1999PPART
DetailsRick Jackson
###-#### TRACY//CONFERENCE 1:00 discussed c/n items with designers and general contractor
INSP - Framing/Rough-in4/29/19994/30/19994/30/1999APART
DetailsJim Storey
04/30/99 301 - fire ceilling systiem supported corectly./canopy framing
INSP - Framing/Rough-in4/27/19994/28/19994/28/1999APART
DetailsRuss Owen
04/28/99 407 - OK REFREGERATION LINES. FOR FIRE CAULKING RIGHT WALL.
INSP - Framing/Rough-in4/26/19994/27/19994/27/1999AFAIL
DetailsJim Storey
04/27/99 301 - support of rc to grid not complet at front of store and n
INSP - Framing/Rough-in4/23/19994/23/19994/23/1999PPART
DetailsJim Storey
04/23/99 301 - ###-#### MEL//SEISMIC BRACING OF GRID CEILING
INSP - Framing/Rough-in4/21/19994/21/19994/21/1999PPART
DetailsJim Storey
04/21/99 301 - south c/f up to 4 ok fo cover
INSP - Framing/Rough-in4/19/19994/19/19994/19/1999PPASS
DetailsJim Storey
04/19/99 301 - ###-#### MEL//FIRE CAULKING MEZZANINE ok
INSP-Conference4/16/19994/16/19994/16/1999PPART
DetailsRick Jackson
fire treated plywodd info okay - sprinklers N/R in pharmacy concealed space
INSP - Framing/Rough-in4/13/19994/14/19994/14/1999APASS
DetailsJim Storey
04/14/99 301 - ###-#### mel//fire caulking
INSP-Conference4/13/19994/13/19994/13/1999APART
DetailsRick Jackson
left c/n for locating sprinklers under refrigeration lines in mezzanine
INSP - Framing/Rough-in4/9/19994/12/19994/12/1999APART
DetailsJim Storey
04/12/99 301 - first bay south end of bldg ok for tile.
INSP-Final Inspection4/9/19994/12/19994/12/1999APART
DetailsRick Jackson
###-#### not a final but sprinkler rough-in inspection - okay to cover sales floor area only.
INSP - Framing/Rough-in4/6/19994/7/19994/7/1999PPART
DetailsJim Storey
04/07/99 301 - Mel ###-#### Conference Seismic Pods on ceiling grids app
INSP - Framing/Rough-in4/5/19994/5/19994/5/1999PFAIL
DetailsJim Storey
04/05/99 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP - Framing/Rough-in3/26/19993/26/19993/26/1999 CANC
DetailsRuss Owen
03/26/99 407 - unable to get this today,to many.
INSP - Framing/Rough-in3/26/19993/26/19993/26/1999PCANC
DetailsRuss Owen
###-#### MEL//FRAMING
INSP - Framing/Rough-in3/19/19993/22/19993/22/1999APART
DetailsJim Storey
03/22/99 301 - ###-#### MEL//SCREW PATTERN ON DRYWALL back/north and sou
INSP - Framing/Rough-in3/16/19993/17/19993/17/1999PPART
DetailsJim Storey
03/17/99 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED ok to start gy
INSP-Supply line flush3/16/19993/16/19993/16/1999PPASS
DetailsRick Jackson
03/16/99 409 - requested by tracy flush okay
INSP - Framing/Rough-in3/11/19993/12/19993/12/1999AFAIL
DetailsJim Storey
03/12/99 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP-Final Inspection3/12/19993/12/19993/12/1999APART
DetailsRick Jackson
###-#### tracy not a final inspection - underground hydro! pass
INSP - Framing/Rough-in3/8/19993/9/19993/9/1999APART
DetailsJim Storey
03/09/99 301 - MEL CONFERENCE ###-#### WILL BE ON SITE
INSP - Framing/Rough-in3/3/19993/4/19993/4/1999AFAIL
DetailsJim Storey
03/04/99 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP-Final Inspection3/3/19993/4/19993/4/1999PPART
DetailsRick Jackson
###-#### not a final - underground inspection only - okay to cover. not installed per plans. requested certification on water flow calcs
INSP - Framing/Rough-in2/16/19992/17/19992/17/1999APART
DetailsJim Storey
02/17/99 301 - SOUTH WALL JOINTS OK TO ROOF DECK INSIDE ONLY, OUTSIDE OK
INSP - Framing/Rough-in2/16/19992/16/19992/16/1999PFAIL
DetailsJim Storey
02/16/99 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP - Framing/Rough-in2/11/19992/11/19992/11/1999PPART
DetailsJim Storey
02/11/99 301 - north half of building roof deeck welding in progess o
INSP - Foundation2/5/19992/5/19992/5/1999 PASS
DetailsJim Storey
/ / 301 - REVIEWED SPECIAL INSP. REPORTS AND ARCHIVED
INSP - Foundation12/4/199812/7/199812/8/1998APART
DetailsRuss Owen
12/08/98 407 - unable to go by subject to special inspection.
INSP - Foundation11/25/199811/25/199811/25/1998PNR
DetailsJim Storey
11/25/98 301 - mel -cell # ###-#### ft insp
INSP - Foundation11/23/199811/24/199811/24/1998APART
DetailsJim Storey
11/24/98 301 - had pre-const meeting with job supper/rick fire russ stru
INSP-Conference11/24/199811/24/199811/24/1998APART
DetailsRick Jackson
fire lanes identified on site plans; reviewed plan check comments with general