Permit Information
Permit NumberBLD98-01998
StatusFinaled
Name IDAHO GASTROENTEROLOGY ASSOCIA
Site Address 425 W BANNOCK ST
Project NameBOISE MEDICAL CENTER
Customer Number 
ePlanReviewNo
Description
To remodel a 6,509 sq.ft. medical office (basement area) in an existing building per approved plans on file. Work to include, Installation of an elevator, construction of a one-hour corridor system, construction of a medical gas storge closet, construction of interior partitions to divide up area for offices, procedure rooms, break room, reception area, electrical room with an emergency generator room, the addition of three fully accessible restrooms, installation of one accessible shower unit, and construction of a one-hour fire resistive wall with 3/4 hour wire glass, 3/4 hour glass blocks, and 3/4 hour doors on electronic hold open devices, to separate the basement from the first floor. This is a type V-1hr building (P.C.#451-98)RMH
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP - Final1/19/19991/20/19991/20/1999PPASS
Details
made ok for perm signed the perm col
INSP-Final Inspection1/19/19991/20/19991/20/1999APASS
DetailsRick Jackson
01/20/99 409 - JR ###-#### occ approved
Permanent Occupancy 1/20/19991/20/1999 DONE
Details
INSP - Final1/8/19991/11/19991/11/1999APART
Details
01/11/99 338 - signed the temp col of the occ req card need hood for the
INSP-Final Inspection1/8/19991/11/19991/11/1999APART
DetailsRick Jackson
JR ###-#### NFPA 72; detector for doors on upper floor; elevator shaft has expsoed wood
INSP - Final1/7/19991/8/19991/8/1999PFAIL
Details
01/08/99 333 - not ready
INSP-Final Inspection1/7/19991/8/19991/8/1999PFAIL
DetailsRick Jackson
JR ###-#### doors in corridor not complete, retest alarms
INSP - Final12/29/199812/30/199812/30/1998AFAIL
Details
12/30/98 333 - not ready left note to Jr that its not ready
INSP-Final Inspection12/22/199812/22/199812/22/1998PFAIL
DetailsRick Jackson
JR ###-#### test generator and alarms; knox box; sprinkler line wrong; label and certify gas; install doors and hardware; extinguishers; penetrations; finish elevator and doors
INSP - Framing/Rough-in12/4/199812/4/199812/4/1998PPART
Details
12/04/98 333 - ceilings ok all but corridors firestops not done in corri
INSP - Framing/Rough-in11/30/199812/1/199812/1/1998APART
Details
12/01/98 333 - conf on ceilings
INSP - Framing/Rough-in11/19/199811/19/199811/19/1998PFAIL
Details
11/19/98 333 - elevator not complete need cover at landings ok to cover
INSP - Framing/Rough-in11/5/199811/5/199811/6/1998PPART
DetailsTom Arcoraci
11/05/98 408 - JR ###-#### ok to vover int walls and lid check shaft for gen set
INSP-Conference11/2/199811/2/199811/2/1998APART
Details
discussed 1 hr ceiling membrane, advised to present assempbly to structural inspector for review to drop 1 hr celing below services. advise the med gas room ventialtion may not be changed without revising plans. smoke damper in coridor was being installed improperly. showed mech contractor and general.
INSP-Sprinkler Rough-in/Hydro10/30/199811/2/199811/2/1998ACANC
DetailsJoe Tawney
11/02/98 406 - jr ###-#### ceiling reading CANCEL TO BE DONE BY 405
INSP - Framing/Rough-in10/29/199810/30/199810/30/1998APART
Details
10/30/98 333 - talked about 1hr wall at entry
INSP - Framing/Rough-in10/15/199810/16/199810/16/1998APART
Details
10/16/98 333 - checked on ada per plan