INSP - Final | 5/24/1999 | 5/25/1999 | 5/25/1999 | A | PASS |
Carl Dependahl
|
|
|
05/25/99 340 - ken ###-####, ok for c.o
|
INSP - Final | 5/24/1999 | 5/24/1999 | 5/24/1999 | | PASS |
Joe Tawney
|
|
|
/ / 406 - REINSP OK FOR PERM OCC
|
Permanent Occupancy | | 5/23/1999 | 5/23/1999 | | DONE |
|
|
|
|
INSP - Final | 5/19/1999 | 5/20/1999 | 5/20/1999 | A | FAIL |
Carl Dependahl
|
|
|
05/20/99 340 - ###-#### KEN//FINAL; need fire ok, has t/o
|
INSP-Final Inspection | 5/20/1999 | 5/20/1999 | 5/20/1999 | | FAIL |
Joe Tawney
|
|
|
05/20/99 406 - ###-#### KEN//FIRE & LIFE SAFETY REINSP FAIL KNOX BOX, FAX OF SIGNALS
|
INSP - Final | 5/17/1999 | 5/18/1999 | 5/18/1999 | A | FAIL |
Carl Dependahl
|
|
|
05/18/99 340 - ###-#### KEN//FINAL; need fire, recall
|
INSP-Final Inspection | 5/17/1999 | 5/18/1999 | 5/18/1999 | A | CANC |
Joe Tawney
|
|
|
05/18/99 406 - REINSP CANCEL RESCHED TO 5/20/99 AT 8:30 AM
|
INSP - Framing/Rough-in | 5/17/1999 | 5/17/1999 | 5/17/1999 | | PART |
Carl Dependahl
|
|
|
/ / 340 - CONF W/ PROJ MGR.
|
INSP - Framing/Rough-in | 5/14/1999 | 5/14/1999 | 5/14/1999 | P | PART |
Carl Dependahl
|
|
|
05/14/99 340 - ken ###-####; ok to use UBC 1016.5 EXC. for rest room doo
|
INSP - Framing/Rough-in | 5/12/1999 | 5/13/1999 | 5/13/1999 | A | NR |
Carl Dependahl
|
|
|
05/13/99 340 - ken ###-#### left msg, not at office
|
INSP - Framing/Rough-in | 5/12/1999 | 5/12/1999 | 5/12/1999 | P | PART |
Carl Dependahl
|
|
|
05/12/99 340 - conf only w/ proj mgr; need arch's letter re smoke dampers, door hdwe; keep c/n.
|
INSP - Framing/Rough-in | 5/11/1999 | 5/11/1999 | 5/11/1999 | P | FAIL |
Carl Dependahl
|
|
|
ken ###-#### call first to meet; keep c/n, need arch's letter re doors & smoke dampers
|
INSP - Final | 4/30/1999 | 4/30/1999 | 4/30/1999 | P | FAIL |
Carl Dependahl
|
|
|
conf w/ proj mgr re corrections, keep c/n.
|
INSP-Final Inspection | 4/29/1999 | 4/30/1999 | 4/29/1999 | A | |
Joe Tawney
|
|
|
Theresa ###-####
|
INSP - Final | 4/27/1999 | 4/27/1999 | 4/27/1999 | | NR |
Carl Dependahl
|
|
|
/ / 340 - CONF W/ BLDR
|
INSP - Final | 4/26/1999 | 4/26/1999 | 4/26/1999 | P | FAIL |
Carl Dependahl
|
|
|
04/26/99 340 - ###-####//TEMP OCCUPY, c/n ok for t/o; card to cont.
|
INSP-Final Inspection | 4/26/1999 | 4/26/1999 | 4/26/1999 | P | PART |
Joe Tawney
|
|
|
FINAL OK FOR TEMP OCC NEED TO RESOLVE S/F DAMPER ISSUE
|
INSP - Final | 4/22/1999 | 4/23/1999 | 4/23/1999 | A | FAIL |
Carl Dependahl
|
|
|
04/23/99 340 - Theresa ###-####; need eng's letter, other sigs, LITES IN
|
INSP-Conference | 4/14/1999 | 4/14/1999 | 4/14/1999 | | PART |
Joe Tawney
|
|
|
/ / 406 - CONF ON LOCATION OF FIRE EXT
|
INSP-Supply line flush | 2/22/1999 | 2/23/1999 | 2/22/1999 | A | |
Russ Owen
|
|
|
###-#### Mike
|
INSP-Conference | 2/10/1999 | 2/10/1999 | 2/10/1999 | | PART |
Joe Tawney
|
|
|
/ / 406 - conf with ken harder & jerry with ESI regarding fire/life sa
|
INSP-Conference | 2/10/1999 | 2/10/1999 | 2/10/1999 | | PART |
Joe Tawney
|
|
|
/ / 406 - conf with ken harder & jerry with ESI regarding fire/life sa
|
INSP - Conference | 2/5/1999 | 2/5/1999 | 2/5/1999 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - conf w/ joe tawney re sprinklers; bldr unaware of req's for etc. keep c/n
|
INSP - Conference | 2/4/1999 | 2/4/1999 | 2/4/1999 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - chk'd previous insp's re frame request 2-4-99
|
INSP - Framing/Rough-in | 2/4/1999 | 2/4/1999 | 2/4/1999 | | FAIL |
Carl Dependahl
|
|
|
/ / 340 - c/n, need fire r/i, resolve plan review issues, firestop rat
|
INSP - Framing/Rough-in | 2/3/1999 | 2/4/1999 | 2/4/1999 | A | CANC |
Russ Owen
|
|
|
02/04/99 407 - trans to 340.
|
INSP - Framing/Rough-in | 1/19/1999 | 1/19/1999 | 1/19/1999 | | PART |
Tom Arcoraci
|
|
|
/ / 408 - bath rooms ok to cover
|
INSP - Framing/Rough-in | 1/19/1999 | 1/19/1999 | 1/19/1999 | | PART |
Tom Arcoraci
|
|
|
/ / 408 - bath rooms ok to cover
|
INSP - Framing/Rough-in | 1/15/1999 | 1/19/1999 | 1/19/1999 | A | PART |
Tom Arcoraci
|
|
|
01/19/99 408 - ###-#### CEILING GRID
|
INSP - Framing/Rough-in | 1/13/1999 | 1/13/1999 | 1/15/1999 | P | PART |
|
|
|
01/13/99 338 - will finish 01/19/99
|
INSP - Framing/Rough-in | 12/28/1998 | 12/28/1998 | 12/28/1998 | P | PART |
|
|
|
12/28/98 338 - made ok to cover with ele insp approval
|
INSP - Foundation | 12/9/1998 | 12/10/1998 | 12/11/1998 | A | PART |
|
|
|
12/11/98 338 - made ok with sp insp approval
|
INSP - Foundation | 12/7/1998 | 12/7/1998 | 12/7/1998 | P | PART |
|
|
|
12/07/98 333 - ok pend spec insp rep
|
INSP - Foundation | 12/4/1998 | 12/4/1998 | 12/4/1998 | P | PART |
|
|
|
12/04/98 338 - MADE OK TO POUR WITH SP INSP APPROVAL
|
INSP - Foundation | 11/23/1998 | 11/23/1998 | 11/23/1998 | P | PART |
|
|
|
11/23/98 338 - made ok with sp insp approval.
|
INSP - Foundation | 11/20/1998 | 11/20/1998 | 11/20/1998 | P | PART |
|
|
|
11/20/98 338 - madeookwith sp insp approval
|
INSP - Foundation | 11/19/1998 | 11/19/1998 | 11/19/1998 | P | |
|
|
|
Scheduled by Hello!. Contact phone is [6584471].
|
INSP - Foundation | 11/18/1998 | 11/18/1998 | 11/19/1998 | P | PART |
|
|
|
11/19/98 338 - madeok with sp insp approval
|
INSP - Foundation | 11/16/1998 | 11/17/1998 | 11/17/1998 | P | PART |
|
|
|
11/17/98 338 - made ok with sp insp approval
|
INSP - Foundation | 11/13/1998 | 11/16/1998 | 11/16/1998 | P | PART |
|
|
|
11/14/98 338 - made ok with sp insp approval
|
INSP - Foundation | 11/13/1998 | 11/16/1998 | 11/16/1998 | P | PART |
|
|
|
11/14/98 338 - made ok with sp insp approval
|
INSP - Foundation | 11/11/1998 | 11/12/1998 | 11/13/1998 | A | PART |
|
|
|
11/12/98 338 - made ok with sp insp approval
|
INSP - Foundation | 11/11/1998 | 11/12/1998 | 11/12/1998 | P | PART |
|
|
|
11/12/98 338 - made ok with sp insp approval next to top and top bond be
|
INSP - Foundation | 11/9/1998 | 11/10/1998 | 11/10/1998 | P | PART |
|
|
|
11/10/98 338 - made ok for pour with sp insp approval
|
INSP - Foundation | 11/6/1998 | 11/9/1998 | 11/9/1998 | A | PART |
|
|
|
11/09/98 338 - made ok for pour with sp insp approvel r-bar placed for g
|
INSP - Foundation | 11/5/1998 | 11/5/1998 | 11/5/1998 | P | PART |
Carl Dependahl
|
|
|
Scheduled by Hello!. Contact phone is [6584471]. pending spec insp report; 338 area.
|
INSP - Foundation | 11/4/1998 | 11/4/1998 | 11/4/1998 | P | PART |
Carl Dependahl
|
|
|
Scheduled by Hello!. Contact phone is [6584471]. 338 area, pending spec insp report.
|
INSP - Foundation | 11/3/1998 | 11/3/1998 | 11/3/1998 | A | PART |
Carl Dependahl
|
|
|
Scheduled by Hello!. Contact phone is [6584471]. pending spec insp. report...338 area.
|
INSP - Foundation | 10/30/1998 | 11/2/1998 | 11/2/1998 | A | FAIL |
|
|
|
11/02/98 333 - no one there
|
INSP - Foundation | 10/29/1998 | 10/30/1998 | 10/30/1998 | A | PART |
|
|
|
10/30/98 338 - made ok with sp insp approval
|
INSP - Foundation | 10/28/1998 | 10/28/1998 | 10/28/1998 | | PART |
|
|
|
10/28/98 338 - made ok to pour bond beam with sp insp approval
|
INSP - Foundation | 10/26/1998 | 10/27/1998 | 10/27/1998 | A | PART |
|
|
|
10/27/98 338 - made ok for bond beam pour with sp insp approval
|
INSP - Framing/Rough-in | 10/23/1998 | 10/26/1998 | 10/26/1998 | A | PART |
|
|
|
10/26/98 338 - MADE OK WITH SP INSP APPROVAL
|
INSP - Foundation | 10/23/1998 | 10/23/1998 | 10/23/1998 | P | PART |
|
|
|
10/23/98 338 - made ok with sp insp approval
|
INSP - Foundation | 10/20/1998 | 10/21/1998 | 10/21/1998 | P | PART |
|
|
|
10/21/98 338 - made o k to pour with sp insp approval
|
INSP - Foundation | 10/19/1998 | 10/19/1998 | 10/19/1998 | P | PART |
|
|
|
10/19/98 338 - made ok with sp insp approval
|
INSP - Framing/Rough-in | 10/14/1998 | 10/15/1998 | 10/15/1998 | A | PART |
|
|
|
10/15/98 338 - MADE OK TO COVER WITH SP INSP APPROVAL
|
INSP - Foundation | 10/12/1998 | 10/12/1998 | 10/14/1998 | P | PART |
|
|
|
10/15/98 338 - made ok with sp insp approval
|
INSP - Foundation | 10/8/1998 | 10/9/1998 | 10/9/1998 | P | PART |
|
|
|
10/09/98 338 - made ok with sp insp blessing
|
INSP - Foundation | 10/6/1998 | 10/7/1998 | 10/7/1998 | A | PART |
|
|
|
10/07/98 338 - MADE OK TO POUR THE BLACK FLOOR AT THE FRONT STAGE AREA
|
INSP - Foundation | 9/29/1998 | 10/1/1998 | 10/1/1998 | P | PART |
Tom Arcoraci
|
|
|
10/01/98 408 - Scheduled by Hello!. Contact phone is [6584471]. spec insp on site
|
INSP - Foundation | 9/24/1998 | 9/25/1998 | 9/25/1998 | P | PART |
|
|
|
09/25/98 338 - MADE OK WITH SP INSP Approval
|
INSP - Foundation | 9/21/1998 | 9/22/1998 | 9/22/1998 | A | PART |
|
|
|
09/22/98 338 - made3 ok with sp insp approval recieved the sp insp lette
|
INSP - Foundation | 9/18/1998 | 9/21/1998 | 9/21/1998 | P | NR |
|
|
|
09/21/98 338 - NOT READY TO POUR SP INSP LETTER NOT ON SITE NO FORMS OR
|