Permit Information
Permit NumberBLD98-03000
StatusFinaled
Name AMERICA'S BEST FURNITURE WAREHOUSE
Site Address 8740 W FAIRVIEW AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
To remodel the 40,592 sq. ft. retail portion of a 69,516 sq. ft. building. No work within the 28,924 sq. ft. warehouse portion. High piled storage racks to remain as originally approved. Work to include the removal of all interior non-bearing display walls, suspended ceiling system, light fixture's & flex duct runs in the retail sales area. To repair existing carpet, paint interior, raise sprinkler system lines to bottom of upper per NFPA #13 as regulated by the fire department, install new light fixtures and attach mechanical diffusers to the existing main duct outlets. Copies of original "Smith Home Furnishings" approved plans from micro fiche #970526 are being used to show limitations of work within the scope of this permit as described herein, for the purpose of obtaining a new Certificate of Occupancy for a new retail tenant. All per approved plans, notes on plans & attachments to plans. PC#98-681/drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP - Final12/1/199812/1/199812/1/1998 PASS
DetailsJoe Tawney
/ / 406 - REINSP OK FOR PERM OCC
Permanent Occupancy 11/27/199811/27/1998 DONE
Details
INSP - Final11/25/199811/25/199811/25/1998PPART
DetailsTom Arcoraci
11/25/98 408 - RAY ###-#### ok for perm occ when others are ok
INSP-Final Inspection11/25/199811/25/199811/25/1998PPASS
DetailsMike Kinnear
RAY ###-#### Two sprinklers were blocked by insulation which the contractor fixed. Owners representative and contractor could not provide the listing of the alarm panel and battery test calculations per NFPA #72 on the same. Contractor signed a certification certificate indicating this was done and he will provide them on the property. Certificate is provided to Joe Tawney (mail box) 11/25/98.
INSP-Conference11/9/199811/9/199811/10/1998PFAIL
DetailsTom Arcoraci
11/09/98 408 - RAY HRAMA ###-####-WANTS TO MAKE SURE FIRE DAMPERS ARE OK FIRE FINAL ALSO. still needs dampers in far west side ducts
INSP - Final11/3/199811/4/199811/4/1998APART
DetailsTom Arcoraci
11/04/98 408 - RAY ###-#### ok for temp needs dampers in ducts has 2 weeks to install
INSP-Final Inspection11/3/199811/3/199811/4/1998PPART
DetailsTom Arcoraci
11/03/98 408 - RAY ###-#### REINSPECT ok for temp occ cr notice issued no fire dampers ins some ducts has 2 we install per bob a.
INSP - Final11/3/199811/3/199811/3/1998 PART
DetailsJoe Tawney
/ / 406 - REINSP OK FOR TEMP OCC EXIT LIGHT, TAPED HEADS, LOOSE INSUL
INSP - Final10/29/199810/30/199810/30/1998AFAIL
DetailsTom Arcoraci
10/30/98 408 - ray- ###-#### fn insp per 325 ducts require dampers
INSP-Final Inspection10/30/199810/30/199810/30/1998PFAIL
Details
ray - temp occ NOne of the sprinkler issues were complete - changed alarm panel to household panel, informed tenant this was not acceptable
INSP-Final Inspection10/30/1998 10/30/1998 TRAN
INSP-Final Inspection10/29/199810/29/199810/29/1998 FAIL
DetailsJoe Tawney
10/29/98 406 - RAY ###-#### FINAL FAIL SPKLR SYSTEM EXIT & EMERG LIGHTS