INSP - Final | 12/1/1998 | 12/1/1998 | 12/1/1998 | | PASS |
Joe Tawney
|
|
|
/ / 406 - REINSP OK FOR PERM OCC
|
Permanent Occupancy | | 11/27/1998 | 11/27/1998 | | DONE |
|
|
|
|
INSP - Final | 11/25/1998 | 11/25/1998 | 11/25/1998 | P | PART |
Tom Arcoraci
|
|
|
11/25/98 408 - RAY ###-#### ok for perm occ when others are ok
|
INSP-Final Inspection | 11/25/1998 | 11/25/1998 | 11/25/1998 | P | PASS |
Mike Kinnear
|
|
|
RAY ###-#### Two sprinklers were blocked by insulation which the contractor fixed. Owners representative and contractor could not provide the listing of the alarm panel and battery test calculations per NFPA #72 on the same. Contractor signed a certification certificate indicating this was done and he will provide them on the property. Certificate is provided to Joe Tawney (mail box) 11/25/98.
|
INSP-Conference | 11/9/1998 | 11/9/1998 | 11/10/1998 | P | FAIL |
Tom Arcoraci
|
|
|
11/09/98 408 - RAY HRAMA ###-####-WANTS TO MAKE SURE FIRE DAMPERS ARE OK FIRE FINAL ALSO. still needs dampers in far west side ducts
|
INSP - Final | 11/3/1998 | 11/4/1998 | 11/4/1998 | A | PART |
Tom Arcoraci
|
|
|
11/04/98 408 - RAY ###-#### ok for temp needs dampers in ducts has 2 weeks to install
|
INSP-Final Inspection | 11/3/1998 | 11/3/1998 | 11/4/1998 | P | PART |
Tom Arcoraci
|
|
|
11/03/98 408 - RAY ###-#### REINSPECT ok for temp occ cr notice issued no fire dampers ins some ducts has 2 we install per bob a.
|
INSP - Final | 11/3/1998 | 11/3/1998 | 11/3/1998 | | PART |
Joe Tawney
|
|
|
/ / 406 - REINSP OK FOR TEMP OCC EXIT LIGHT, TAPED HEADS, LOOSE INSUL
|
INSP - Final | 10/29/1998 | 10/30/1998 | 10/30/1998 | A | FAIL |
Tom Arcoraci
|
|
|
10/30/98 408 - ray- ###-#### fn insp per 325 ducts require dampers
|
INSP-Final Inspection | 10/30/1998 | 10/30/1998 | 10/30/1998 | P | FAIL |
|
|
|
ray - temp occ NOne of the sprinkler issues were complete - changed alarm panel to household panel, informed tenant this was not acceptable
|
INSP-Final Inspection | 10/30/1998 | | 10/30/1998 | | TRAN |
|
|
|
|
INSP-Final Inspection | 10/29/1998 | 10/29/1998 | 10/29/1998 | | FAIL |
Joe Tawney
|
|
|
10/29/98 406 - RAY ###-#### FINAL FAIL SPKLR SYSTEM EXIT & EMERG LIGHTS
|