Permit Information
Permit NumberBLD99-01672
StatusFinaled
Name HEWLETT-PACKARD ATT: OLGA
Site Address 303 N KIMBALL ST
Project NameHP #26
Customer Number46B11152
ePlanReviewNo
Description
TO COMPLETE THE INTERIOR OF A NEW SHELL BUILDING INTO OFFICE SPACE WITH RESTROOMS AND MECHANCIAL ROOM FOR SWITCH GEAR. WORK TO INCLUDE NEW SUSPENDED CEILING, NON-RATED INTERIOR PARTITIONS OF STEEL STUD A GYP. BOARD AND OTHER RELATED WORK PER APPROVED PLANS AND ATTACHMENTS. THIS BUILDING IS FULLY FIRE SPRINKLERED FOR AREA INCREASE.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final11/8/199911/9/199911/9/1999PPASS
DetailsCarl Dependahl
KENT ###-#### Card to cont.
Permanent Occupancy 11/9/199911/9/1999 DONE
Details
BLD-Final11/5/199911/8/199911/8/1999PFAIL
DetailsCarl Dependahl
KEN ###-#### Keep C/N, has T/O
FIRE-Final Inspection10/20/199910/22/199910/22/1999PPASS
DetailsJoe Tawney
MIKE ###-#### FN FIRE Reinsp. Ok for permanent occupancy
BLD-Final10/14/199910/15/199910/15/1999AFAIL
DetailsCarl Dependahl
KENT--- ###-#### FN OCC Ok for T/O- C/N: handrails, misc. finish, other finals.
FIRE-Final Inspection10/12/199910/13/199910/13/1999PPART
DetailsJoe Tawney
Mike ###-#### Ok for Temporary occupancy per Lan Smith
BLD-Framing/Rough-in10/11/199910/12/199910/12/1999AFAIL
DetailsCarl Dependahl
CONFERENCE Mike Hatash ###-#### Need elec. Final
FIRE-Hydro test above ground10/7/199910/7/199910/7/1999APART
DetailsJoe Tawney
okay for an above ground hrdro test
FIRE-Supply Line Hydro10/6/199910/6/199910/6/1999PFAIL
DetailsJoe Tawney
Jeff ###-#### hydro test fail reschedule
BLD-Framing/Rough-in9/28/19999/28/19999/28/1999PPART
DetailsWes Worcester
CEILING GRID KENT ###-#### Need installation criteria, entrance not done, ok to drop panels
BLD-Framing/Rough-in9/23/19999/24/19999/23/1999AFAIL
DetailsWes Worcester
GRID CEILING #26 KENT ###-#### Seismic pods & spreader bars to be installed per Mfg's specs
FIRE-Sprinkler Rough-in9/23/19999/23/19999/23/1999PPART
DetailsJoe Tawney
JEFF-- ###-#### R/I FOR FIRE Ok on sprinkler system R/I
Sprinkler Rough-in9/9/19999/9/19999/9/1999PPART
DetailsJoe Tawney
R/I ok pm preaction sprlr system - ok to cover
INSP - Framing/Rough-in8/17/19998/18/19998/18/1999APART
DetailsWes Worcester
08/18/99 342 - one hr walls not done, 45 brace missing above door at rea
INSP - Framing/Rough-in7/26/19997/27/19997/27/1999APART
DetailsCarl Dependahl
07/27/99 340 - hard lid at telecom rm, need see roof drain areaScheduled