BLD-Conference | 3/21/2002 | 3/21/2002 | 3/21/2002 | A | PASS |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 3/21/2002 9:49:49 AM rec'd Final Mti report verifying proper adhesion of fireproofing, c/n ok. 3/21/2002 10:14:03 AM
|
BLD-Final | 3/21/2002 | 3/21/2002 | 3/21/2002 | A | PASS |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 3/21/2002 10:06:49 AM c/n ok...ok for perm l/c only. 3/21/2002 11:18:23 AM
|
BLD-Final | 3/21/2002 | 3/21/2002 | 3/21/2002 | P | PASS |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 3/21/2002 10:15:08 AM ok for l/c 3/21/2002 2:09:07 PM
|
FIRE-Final Inspection | 3/21/2002 | 3/21/2002 | 3/21/2002 | P | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 3/21/2002 3:03:08 PM
|
BLD-Final | 3/8/2002 | 3/11/2002 | 3/11/2002 | A | FAIL |
Carl Dependahl
|
|
|
mel ###-#### fn occ ; verify fireproofing approval re MTI affidavit, reports 375 &386. rec'd statement of repair from ISI (Kip Frawley, spray-on mgr.) but no approval or acknowledgement from arch.3/11/2002 4:03:12 PM 3/11/2002 4:06:22 PM
|
BLD-Final | 1/2/2002 | 1/2/2002 | 1/2/2002 | P | FAIL |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 1/2/2002 3:20:31 PM c/n, need eng'rs complete response to spec insp items, permanent oks from all agencys, previous corrections completed, etc . ok for t/o only per P&Z (Tempra)
|
BLD-Final | 12/28/2001 | 12/31/2001 | 12/31/2001 | A | NR |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 12/28/2001 at 17:41:37. Contact: ###-####...keep c/n. 12/31/2001 5:49:23 PM
|
FIRE-Final Inspection | 12/27/2001 | 12/28/2001 | 12/28/2001 | P | FAIL |
Rick Jackson
|
|
|
###-#### door hardware; closures; with Carl D and Lee 12/28/2001 4:52:50 PM
|
BLD-Conference | 12/12/2001 | 12/12/2001 | 12/12/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 12/12/2001 6:04:02 PM need eng's, arch's, & spec insp reports
|
BLD-Conference | 11/29/2001 | 11/29/2001 | 11/29/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 11/29/2001 2:27:21 PM ok to delete 1hr const at north wall except at & above sally port closer than 39' to P.L. per waiver request approved by T. Hogland.
|
BLD-Energy code compliance | 11/26/2001 | 11/27/2001 | 11/27/2001 | A | NR |
Carl Dependahl
|
|
|
LORA ###-####; need arch's approval /letter to delete 1hr const at north wall. will submit 11/27/2001 1:48:52 PM
|
BLD-Framing/Rough-in | 11/27/2001 | 11/27/2001 | 11/27/2001 | P | FAIL |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 11/27/2001 1:47:41 PM bsmt: c/n re corridor penetrations, lg. panel box at elec. rm... grid wires, pods;labels at rated doors & glass. repair spray-on F.P. at beams, pan over garage, etc. Verify fire-smoke dampers at hvac at elev lobbies/corridor. ok to tile 2hr exit pass. at 1st fl, grid ok.
|
BLD-Conference | 11/26/2001 | 11/26/2001 | 11/26/2001 | A | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 11/26/2001 11:23:41 AM w/ George Eidam, Eidam eng's...need standby power for one elevator to 5th floor per UBC 1104; 4th floor ok per exception.
|
BLD-Conference | 11/16/2001 | 11/16/2001 | 11/16/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 11/16/2001 11:08:44 AM w/ 409 re ADA req't for standby power to 1 elevator, per UBC1104.1.3...will advise bldr.
|
BLD-Conference | 11/8/2001 | 11/8/2001 | 11/8/2001 | A | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 11/8/2001 10:11:26 AM rec'd, reviewed insp reports...soils at west side entry retest ok per mti
|
BLD-Conference | 9/20/2001 | 9/20/2001 | 9/20/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 9/20/2001 6:01:57 PM need repair fireproofing at" new" add'l beams...verbal c/n.
|
BLD-Framing/Rough-in | 9/5/2001 | 9/5/2001 | 9/5/2001 | P | FAIL |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 9/5/2001 3:42:07 PM need recheck spray on fire proofing removed at col's /spandrels & secondary floor supports attached after-the-fact...MTI report req'd.
|
BLD-Conference | 8/21/2001 | 8/21/2001 | 8/21/2001 | P | PASS |
Carl Dependahl
|
|
|
Scheduled by Inspector: 340 On 8/21/2001 9:48:11 AM mel ###-#### shell...need all reports 8/21/2001 4:38:23 PM
|
BLD-Conference | 6/14/2001 | 6/14/2001 | 6/14/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 6/14/2001 3:21:02 PM data boxes at floor, wip ok
|
BLD-Framing/Rough-in | 6/7/2001 | 6/7/2001 | 6/7/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 6/7/2001 4:39:19 PM ext gfrc panels
|
BLD-Framing/Rough-in | 5/31/2001 | 5/31/2001 | 5/31/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 5/31/2001 3:33:20 PM with Mel P... keep c/n, install shaft for hvac at NE corner area, fl 3-5...
|
BLD-Framing/Rough-in | 5/16/2001 | 5/16/2001 | 5/16/2001 | P | FAIL |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 5/16/2001 5:12:55 PM keep c/n re shafts, 4hr & 2hr occ separations.
|
BLD-Framing/Rough-in | 5/11/2001 | 5/11/2001 | 5/11/2001 | P | FAIL |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 5/11/2001 4:17:01 PM need shafts at hvac exhaust thru floors 3,4; clarify masonry const for 4hr wall at bsmt...cl. B-4 blocks req'd?
|
BLD-Framing/Rough-in | 5/3/2001 | 5/3/2001 | 5/3/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 5/3/2001 4:52:54 PM curtain wall firestops at fls.2,3,4,5 appear ok...mti also inspecting
|
BLD-Framing/Rough-in | 4/30/2001 | 4/30/2001 | 4/30/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 4/30/2001 5:00:36 PM firestops at 3rd fl curtain wall/floor...ok; has mti insp. too.
|
BLD-Framing/Rough-in | 4/13/2001 | 4/13/2001 | 4/13/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 4/13/2001 2:01:03 PM 2nd fl curtain wall firestops...wip
|
BLD-Framing/Rough-in | 4/12/2001 | 4/12/2001 | 4/12/2001 | A | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 4/12/2001 10:50:31 AM continuing insp...firestops 2nd fl east side...rework gaps, holes. wip
|
BLD-Framing/Rough-in | 4/11/2001 | 4/11/2001 | 4/11/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 4/11/2001 5:44:30 PM 2nd fl curtain wall firestops at north & east sides ok per detail; wip for shafts, & corridor walls
|
BLD-Conference | 4/9/2001 | 4/9/2001 | 4/9/2001 | A | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 4/9/2001 10:02:48 AM w/ Mel Perez, supt. re floor/curtainwall firestop assy 4/9/2001 10:03:20 AM
|
BLD-Conference | 2/27/2001 | 2/27/2001 | 2/27/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 2/27/2001 5:58:11 PM faxed floor detail for penetrations
|
BLD-Conference | 2/21/2001 | 2/21/2001 | 2/21/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 2/21/2001 4:07:37 PM w/ Laura Patten re 2hr fl assy...eng'd judgement to be provided for protection of boxes
|
BLD-Conference | 2/8/2001 | 2/8/2001 | 2/8/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 2/8/2001 4:25:07 PM gave list of questions for clarification to proj. eng'r re floor penetrations
|
BLD-Conference | 2/5/2001 | 2/5/2001 | 2/5/2001 | P | PASS |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 2/5/2001 12:04:55 PM w/ proj engr; resub. re boxes
|
BLD-Conference | 2/1/2001 | 2/1/2001 | 2/1/2001 | P | PASS |
Carl Dependahl
|
|
|
Laura Patton ###-####; rec'd resub for floor boxes, will advise..discussed handrails w/ supt. 2/2/2001 12:01:02 PM
|
BLD-Conference | 2/1/2001 | 2/1/2001 | 2/1/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 2/1/2001 4:53:27 PM w/Laura re fl boxes
|
BLD-Conference | 1/11/2001 | 1/11/2001 | 1/11/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 1/11/2001 5:13:50 PM walk thru
|
BLD-Conference | 1/9/2001 | 1/9/2001 | 1/9/2001 | P | PART |
Carl Dependahl
|
|
|
Added by Inspector: 340 On 1/9/2001 6:10:07 PM w/ super, proj engr at sitr. need submittal for floor boxes
|