BLD-Final | 5/1/2001 | 5/1/2001 | 5/1/2001 | P | PART |
Tony Young
|
|
|
Scheduled by a contractor via Hello! on 05/01/2001 at 11:18:49. Contact: ###-####.
c/n on verification of smoke seal rating in corridor vs. fire rated (astricals) also need final reports from special inspections, temp. occ. signed 5/1/2001 3:50:26 PM
|
BLD-Final | 4/20/2001 | 4/23/2001 | 4/23/2001 | P | FAIL |
Steven Webb
|
|
|
Scheduled by a contractor via Hello! on 04/20/2001 at 07:38:50. Contact: ###-####. c/n issued- 4/23/2001 4:01:15 PM
|
FIRE-Alarm Testing | 4/12/2001 | 4/13/2001 | 4/13/2001 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/12/2001 at 11:49:58. Contact: .
|
FIRE-Final Inspection | 4/12/2001 | 4/13/2001 | 4/13/2001 | A | PASS |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/12/2001 at 11:49:13. Contact: .
|
BLD-Final | 3/28/2001 | 3/30/2001 | 3/30/2001 | P | NR |
Steven Webb
|
|
|
Scheduled by a contractor via Hello! on 03/28/2001 at 10:13:22. Contact: ###-####. All required sign-offs not done-will reschedule. 3/30/2001 12:41:34 PM
|
FIRE-Final Inspection | 4/2/2001 | 3/30/2001 | 3/30/2001 | P | FAIL |
Rick Jackson
|
|
|
Added by Inspector: 409 On 4/2/2001 8:30:24 AM c/n issued
|
BLD-Wall cover | 1/18/2001 | 1/19/2001 | 1/19/2001 | A | PASS |
Steven Webb
|
|
|
|
BLD-Framing/Rough-in | 12/6/2000 | 12/6/2000 | 12/6/2000 | P | PART |
Steven Webb
|
|
|
Scheduled by a contractor via Hello! on 12/06/2000 at 08:53:33. Contact: ###-####. remaining corridor, conference rooms. 12/6/2000 3:57:25 PM
|
BLD-Framing/Rough-in | 11/17/2000 | 11/20/2000 | 11/20/2000 | A | PART |
Tony Young
|
|
|
Scheduled by a contractor via Hello! on 11/17/2000 at 08:44:50. Contact: ###-####.
part of interior walls ok to cover or insulate, also part of ceiling 11/20/2000 10:52:23 AM
|
BLD-Framing/Rough-in | 10/31/2000 | 11/1/2000 | 11/1/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 10/31/2000 at 10:31:35. Contact: .
|
BLD-Framing/Rough-in | 10/23/2000 | 10/24/2000 | 10/24/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 10/23/2000 at 16:30:02. Contact: .still waiting for details for ceiling. 10/24/2000 11:55:31 AM
|
BLD-Framing/Rough-in | 10/17/2000 | 10/18/2000 | 10/18/2000 | A | CANC |
Tom Arcoraci
|
|
|
somebody will be on site
|
BLD-Framing/Rough-in | 10/18/2000 | 10/18/2000 | 10/18/2000 | P | PART |
Russ Owen
|
|
|
Added by Inspector: 407 On 10/18/2000 ceiling details needed,fresh air chase,top of ext wall detail,c/n posted architect of record to address.
|
BLD-Framing/Rough-in | 10/9/2000 | 10/10/2000 | 10/10/2000 | A | NR |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 10/09/2000 at 16:14:10. Contact: .
|
BLD-Framing/Rough-in | 10/9/2000 | 10/9/2000 | 10/9/2000 | A | PART |
Russ Owen
|
|
|
Added by Inspector: 407 On 10/9/2000 ok to cover roof decking.
|
BLD-Framing/Rough-in | 10/6/2000 | 10/9/2000 | 10/9/2000 | A | PART |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 10/06/2000 at 12:31:12. Contact: .
|
BLD-Framing/Rough-in | 10/4/2000 | 10/5/2000 | 10/5/2000 | P | PART |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 10/04/2000 at 12:56:40. Contact: .roof nailing 10/5/2000 4:02:49 PM
|
BLD-Framing/Rough-in | 9/29/2000 | 9/29/2000 | 9/29/2000 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 09/29/2000 at 08:53:01. Contact: .roof nail.need more. 9/29/2000 1:53:20 PM
|
BLD-Concrete | 9/5/2000 | 9/6/2000 | 9/6/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 09/05/2000 at 15:55:38. Contact: ###-####. Subject to SI. 9/6/2000 11:52:01 AM
|
BLD-Footing | 8/11/2000 | 8/11/2000 | 8/11/2000 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 08/11/2000 at 08:05:32. Contact: ###-####.
|
BLD-Concrete | 8/8/2000 | 8/9/2000 | 8/9/2000 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 08/08/2000 at 06:41:50. Contact: ###-####.
|
BLD-Concrete | 8/8/2000 | 8/8/2000 | 8/8/2000 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 08/08/2000 at 06:41:03. Contact: ###-####. Subject to si. 8/9/2000 8:38:47 AM
|
BLD-Concrete | 7/31/2000 | 8/2/2000 | 8/2/2000 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 07/31/2000 at 09:26:14. Contact: ###-####. Subject to s/i. 8/3/2000 8:14:46 AM
|
BLD-Concrete | 7/31/2000 | 7/31/2000 | 7/31/2000 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 07/31/2000 at 09:25:26. Contact: ###-####. subject to S-I 8/1/00 4:47:05 PM
|
BLD-Footing | 7/20/2000 | 7/21/2000 | 7/21/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 07/20/2000 at 13:39:33. Contact: ###-####. Subject to S-I 7/21/00 2:14:51 PM
|
BLD-Concrete | 7/17/2000 | 7/18/2000 | 7/18/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 07/17/2000 at 16:08:43. Contact: ###-####. Subject to SI 7/18/00 2:22:59 PM
|
BLD-Concrete | 7/12/2000 | 7/13/2000 | 7/13/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 07/12/2000 at 13:25:59. Contact: ###-####. Subject ot SI 7/14/00 9:03:03 AM
|
BLD-Footing | 7/12/2000 | 7/13/2000 | 7/13/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 07/12/2000 at 13:25:22. Contact: ###-####. Subject to SI 7/14/00 9:04:05 AM
|
BLD-Concrete | 7/6/2000 | 7/11/2000 | 7/11/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 07/06/2000 at 15:22:10. Contact: ###-####. Subject to SI 7/12/00 10:34:59 AM
|
BLD-Footing | 7/10/2000 | 7/11/2000 | 7/11/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 07/10/2000 at 16:50:25. Contact: ###-####. Subject to SI 7/12/00 10:35:07 AM
|
BLD-Foundation | 7/6/2000 | 7/7/2000 | 7/7/2000 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 07/06/2000 at 15:21:22. Contact: ###-####. Subject to SI 7/10/00 10:29:54 AM
|
BLD-Footing | 6/29/2000 | 6/30/2000 | 6/30/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 06/29/2000 at 14:25:11. Contact: ###-####. subject to S-I. 6/30/00 3:22:06 PM
|
BLD-Foundation | 6/23/2000 | 6/26/2000 | 6/26/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 06/23/2000 at 14:34:53. Contact: ###-####. Need SI reports, notified general contractor. 6/26/00 3:00:04 PM
|
BLD-Concrete | 6/16/2000 | 6/19/2000 | 6/19/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 06/16/2000 at 12:55:22. Contact: ###-####. subject to S-I 6/19/00 2:20:57 PM
|
BLD-Foundation | 6/15/2000 | 6/16/2000 | 6/16/2000 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 06/15/2000 at 15:00:14. Contact: ###-####. covered under spical insp. 6/16/00 12:33:02 PM
|
BLD-Other | 6/15/2000 | 6/16/2000 | 6/16/2000 | A | PART |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 06/15/2000 at 15:02:16. Contact: ###-####. covered under special insp. 6/16/00 12:33:17 PM
|
BLD-Foundation | 6/13/2000 | 6/14/2000 | 6/14/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 06/13/2000 at 16:18:46. Contact: ###-####. Subject to S-I. 6/14/00 3:34:05 PM
|
BLD-Footing | 6/9/2000 | 6/12/2000 | 6/12/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 06/09/2000 at 11:49:21. Contact: ###-####. subject to s/i. 6/13/00 10:03:25 AM
|
BLD-Footing | 6/8/2000 | 6/9/2000 | 6/9/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 06/08/2000 at 12:44:34. Contact: ###-####. s/i report pending 6/13/00 10:00:26 AM
|
BLD-Foundation | 6/5/2000 | 6/6/2000 | 6/6/2000 | A | PART |
Carl Dependahl
|
|
|
Scheduled by a contractor via Hello! on 06/05/2000 at 16:06:24. Contact: ###-####. Spec. insp onsite pend report 6/7/00 10:05:01 AM
|
BLD-Foundation | 6/1/2000 | 6/2/2000 | 6/2/2000 | A | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 06/01/2000 at 15:46:18. Contact: ###-####. Subject to S/I by strata 6/5/00 10:53:32 AM
|
BLD-Footing | 5/24/2000 | 5/25/2000 | 5/25/2000 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 05/24/2000 at 10:59:29. Contact: . Subject to S-I by Strata 5/31/00 9:14:07 AM
|
FIRE-Supply Line Flush | 5/24/2000 | 5/25/2000 | 5/25/2000 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 05/24/2000 at 13:20:04. Contact: ###-####. Need permit underground; not coated per NFPA 2Y 5/25/00 1:41:44 PM
|
BLD-Footing | 5/22/2000 | 5/23/2000 | 5/23/2000 | P | PART |
Russ Owen
|
|
|
Scheduled by a contractor via Hello! on 05/22/2000 at 10:50:04. Contact: ###-####. Subject to S-I, by Strata 5/24/00 1:44:21 PM
|