Final | 1/18/2001 | 1/19/2001 | 1/19/2001 | A | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 01/18/2001 at 15:53:24. Contact: ###-####. ok final 1/19/2001 12:05:48 PM
|
Final | 11/29/2000 | 11/29/2000 | 11/29/2000 | P | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 11/29/2000 at 10:10:07. Contact: ###-####. 324 & 412 went out ok temp occ. per tim hogland. corr. no third party testing on remote radiator & 4 vent fans on roof. no inspection on back up battery inverters work not completed. 11/29/2000 4:06:40 PM
|
Permanent Service | 11/20/2000 | 11/21/2000 | 11/21/2000 | P | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 11/20/2000 at 15:56:16. Contact: ###-####. this inspection was for temp occ. failed need third party testing strickers on 4 vent fans on roof & on radiator for generator 11/21/2000 4:22:53 PM
|
Temporary Service | 11/14/2000 | 11/14/2000 | 11/14/2000 | P | FAIL |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 11/14/2000 at 08:15:02. Contact: ###-####. this inspection is for temp. occ. failed corr. nec 110-3(b)3rd party listing for 4 vent fans on roof, generator remote radiator, & ground clamps for main service nec110-26(b) working space for radiator disconnect 42" 11/14/2000 4:42:09 PM
|
Final | 11/9/2000 | 11/13/2000 | 11/13/2000 | A | NR |
Mike Kinnear
|
|
|
temp occ\###-#### need to locate 3rd party testing strickers 11/13/2000 4:08:01 PM no strickers on 4 roof vent fans & radiator for generator 11/13/2000 4:09:38 PM
|
Permanent Service | 9/26/2000 | 9/27/2000 | 9/27/2000 | A | PASS |
Mike Kinnear
|
|
|
Kelly Smith ###-#### Third party lable found ok 9/29/00 11:10:22 AM
|
Permanent Service | 9/22/2000 | 9/25/2000 | 9/25/2000 | A | FAIL |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 09/22/2000 at 13:01:48. Contact: ###-####. Correction need third party lable on generator. 9/26/00 11:36:03 AM
|
Electrical Rough-In | 9/19/2000 | 9/19/2000 | 9/19/2000 | P | PASS |
Mike Kinnear
|
|
|
KELLY --###-#### R/I Ok cover ceiling 9/21/00 4:25:52 PM
|
Permanent Service | 9/11/2000 | 9/11/2000 | 9/11/2000 | P | PASS |
Mike Kinnear
|
|
|
kelly ###-#### pager per ser P/S U/G reconnect ok 9/12/00 11:00:58 AM
|
Electrical Rough-In | 7/11/2000 | 7/12/2000 | 7/12/2000 | A | PART |
Jack Frank
|
|
|
###-#### Restroom & storage ok 7/13/00 11:25:54 AM
|
Electrical Rough-In | 6/29/2000 | 6/30/2000 | 6/30/2000 | A | PART |
Jack Frank
|
|
|
Kelly SMith ###-#### walls ok 6/30/00 3:09:28 PM
|