Final | 2/11/2003 | 2/12/2003 | 2/12/2003 | A | PASS |
Jack Frank
|
|
|
RE-INSP NATE; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok card signed 2/12/2003 4:22:03 PM
|
Final | 1/29/2003 | 1/29/2003 | 1/29/2003 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung cor. $42.00 fee due posted met contractor strap LFMC, 12inches of boxes RMC 3ft of boxes, tighten all clamps and bond bushings, install bond bushins all RMC nipples out of back of boxes 1/29/2003 3:59:48 PM
|
Electrical Rough-In | 12/6/2002 | 12/6/2002 | 12/6/2002 | P | PART |
Jack Frank
|
|
|
conference with contractor concerning correction notice posted
|
Final | 11/14/2002 | 11/14/2002 | 11/14/2002 | P | FAIL |
Jack Frank
|
|
|
###-#### russell job not ready partial correction posted 110.3(B) install grd bushings on all conduits entering non metallic boxes manufactrues instructionssupport all raceways and secure within 3 ft of boxes 314.25,250.110,406.5 grd all covers u/g jboxes 11/14/2002 6:18:01 PM
|
Electrical Rough-In | 10/16/2002 | 10/17/2002 | 10/17/2002 | P | PASS |
Jack Frank
|
|
|
###-#### UNDER GRND. ok 10/17/2002 6:37:48 PM
|
Electrical Rough-In | 10/16/2002 | 10/16/2002 | 10/16/2002 | P | PART |
Jack Frank
|
|
|
underground cover -east end of roadway -casey -###-#### ok 10/16/2002 5:14:33 PM
|
Electrical Rough-In | 10/9/2002 | 10/10/2002 | 10/10/2002 | A | PART |
Jack Frank
|
|
|
RUSSEL; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 10/10/2002 2:16:00 PM
|
Electrical Rough-In | 8/30/2002 | 9/3/2002 | 9/3/2002 | P | PASS |
Jack Frank
|
|
|
###-#### u/g conduit ok 9/3/2002 6:15:57 PM
|
Electrical Rough-In | 8/26/2002 | 8/27/2002 | 8/27/2002 | A | PART |
Jack Frank
|
|
|
###-#### u/g ok called contractor shall not ID 6, or smaller neutrals or equipment grds 8/27/2002 3:16:17 PM
|
Electrical Rough-In | 7/18/2002 | 7/19/2002 | 7/19/2002 | P | PART |
Jack Frank
|
|
|
RUSSELL; Phone #: ###-#### u/g ok on dirt bank south of new raised road, in front of new terminal 7/19/2002 4:19:28 PM
|
Electrical Rough-In | 7/11/2002 | 7/12/2002 | 7/12/2002 | A | PART |
Jack Frank
|
|
|
russel ###-#### part for u/g conduit ok 7/12/2002 12:17:27 PM
|
Electrical Rough-In | 6/10/2002 | 6/11/2002 | 6/11/2002 | P | FAIL |
Mike Kinnear
|
|
|
underground on westside of bridge--russell- ###-#### called left message need to talk to contractor over 360 degrees of bend ? 6/11/2002 6:29:46 PM
|
Electrical Rough-In | 6/11/2002 | 6/11/2002 | 6/11/2002 | P | PART |
Jack Frank
|
|
|
u/g ok partial
|
Electrical Rough-In | 6/5/2002 | 6/6/2002 | 6/6/2002 | P | PASS |
Tim McCullough
|
|
|
###-####- russell
pour ri ok 6/6/2002 11:24:55 AM
|
Electrical Rough-In | 5/24/2002 | 5/28/2002 | 5/28/2002 | A | PASS |
Tim McCullough
|
|
|
UNDERGROUND COVER ###-#### RUSSEL
ok cover parking area
5/28/2002 1:55:57 PM
|
Electrical Rough-In | 5/16/2002 | 5/17/2002 | 5/17/2002 | P | PART |
Jack Frank
|
|
|
###-#### underground for 5 pole bases ok 5/17/2002 4:32:27 PM
|
Electrical Rough-In | 5/3/2002 | 5/3/2002 | 5/3/2002 | P | PART |
Pat Lass
|
|
|
for underground- justin -###-####
|
Final | 4/29/2002 | 4/30/2002 | 4/30/2002 | A | PART |
Jack Frank
|
|
|
###-#### RUSSELL u/g for fixtures in raised roadway 4/30/2002 11:06:11 AM
|
Electrical Rough-In | 4/1/2002 | 4/2/2002 | 4/2/2002 | P | FAIL |
Jack Frank
|
|
|
ok to cover- russell ###-####-
met with contractor at job site corrections noted 344.26,352.26 over 360 degrees of bends in u/g conduit 4/2/2002 4:04:19 PM
|
Electrical Rough-In | 3/27/2002 | 3/27/2002 | 3/27/2002 | P | PART |
Jack Frank
|
|
|
###-#### RUSSEL u/g conduits ok for cover 3/27/2002 6:02:35 PM
|
Rough-In Permanent Service | 2/21/2002 | 2/22/2002 | 2/22/2002 | P | PART |
Pat Lass
|
|
|
###-#### RUSSEL CALL 1ST beams ok 2/22/2002 4:54:43 PM
|
Electrical Rough-In | 2/15/2002 | 2/15/2002 | 2/15/2002 | P | PASS |
Jim Schmer
|
|
|
cover insp --russell ###-#### call 1st before insp
|
ELE-Aging Inspection | 12/31/2001 | 12/31/2001 | 12/31/2001 | | PART |
Jack Frank
|
|
|
W S U C 12/31/2001 2:54:08 PM
|
Electrical Rough-In | 10/30/2001 | 10/30/2001 | 10/30/2001 | P | PART |
Pat Lass
|
|
|
###-#### RUSSEL
|
Electrical Rough-In | 10/24/2001 | 10/25/2001 | 10/25/2001 | P | PART |
Jack Frank
|
|
|
###-#### russ some pvc in concrete pour 10/25/2001 4:28:23 PM
|
Electrical Rough-In | 10/22/2001 | 10/23/2001 | 10/23/2001 | P | NR |
Jack Frank
|
|
|
###-#### RUSSEL they will call when ready 10/23/2001 12:33:20 PM
|
Electrical Rough-In | 10/4/2001 | 10/4/2001 | 10/4/2001 | P | PASS |
Jack Frank
|
|
|
russell-- ###-#### or scott ###-#### r/i columns ok 10/4/2001 4:13:51 PM
|
Electrical Rough-In | 9/28/2001 | 10/1/2001 | 10/1/2001 | A | PART |
Pat Lass
|
|
|
###-#### RUSS ###-#### colums ok 10/1/2001 10:35:18 AM
|
Electrical Rough-In | 9/26/2001 | 9/26/2001 | 9/26/2001 | P | PART |
Jack Frank
|
|
|
###-#### russell 2 columns 9/26/2001 4:07:06 PM
|
Electrical Rough-In | 9/21/2001 | 9/21/2001 | 9/21/2001 | P | PART |
Jack Frank
|
|
|
2 columns on west end Russell ###-#### ok 9/21/2001 4:19:11 PM
|
Electrical Rough-In | 9/18/2001 | 9/18/2001 | 9/18/2001 | P | CANC |
Jack Frank
|
|
|
russell ###-#### contractor called and asked me to cancel inspection 9/18/2001 5:38:19 PM
|
Electrical Rough-In | 9/4/2001 | 9/5/2001 | 9/5/2001 | A | PART |
Jack Frank
|
|
|
r/i- russell ###-####- cover for columns ok 9/5/2001 9:47:49 AM
|
Electrical Rough-In | 8/30/2001 | 8/31/2001 | 8/31/2001 | A | PART |
Jack Frank
|
|
|
russell ###-#### r/i wiring in columns ok 8/31/2001 10:00:19 AM
|
Electrical Rough-In | 8/28/2001 | 8/28/2001 | 8/28/2001 | P | PART |
Jack Frank
|
|
|
COVER INSP- TIM CELL ###-####- OR RICK ###-#### -CALL TIM 1ST BEFORE INSP 4 light standards ok 8/28/2001 3:23:25 PM
|