Permit Information
Permit NumberELE02-01340
StatusFinaled
Name ALLOWAY ELECTRIC CO INC
Site Address 6622 W DORIAN ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/19/20026/20/20026/20/2002APASS
DetailsJack Frank
ELEN ###-#### PLEASE CALL BEFORE SO ELEN CAN MEET YOU THERE ok 6/20/2002 10:53:19 AM
Permanent Service6/20/20026/20/20026/20/2002APASS
DetailsJack Frank

p/s o/h rec. ok
Permanent Service6/10/20026/10/20026/10/2002PFAIL
DetailsJack Frank
for homeowner call 1st before insp- ###-####-ellen all correcdtion s not made called need to grd to u/g water pipe within 5 ft of where it enters or verify that there is less than 10 ft of metal u//g water pipe in contact with earth 6/10/2002 5:01:39 PM
Final5/28/20025/29/20025/29/2002ANH
DetailsTim McCullough
ellen ###-#### call 1stc
called 9:45 am & 2:24 pm 5/29/2002 4:10:47 PM
Electrical Rough-In5/8/20025/9/20025/9/2002PPART
DetailsJack Frank
JERRY ###-#### CONF ONLY met with contractor went over corrections, contractor said the code is stupid 5/9/2002 3:08:04 PM
Final5/7/20025/8/20025/8/2002AFAIL
DetailsJack Frank
call first 20 min. for access ###-#### cor. posted called 250.52 or 104 grd or bond, 300.10 bond bushing for all R E washers110.26 clearence dedicated space headrm 230.28 BBC U bolt guy kit, what is grd or bond wire at sub panel, that should all be done p/s 5/8/2002 11:04:43 AM
Permanent Service5/6/20025/7/20025/7/2002PNH
DetailsJack Frank
Scheduled by a contractor via Hello! on 05/06/2002 at 14:30:58. Contact: ###-####. no access called contractor will reschedule 5/7/2002 4:39:02 PM