Final | 8/12/2002 | 8/12/2002 | 8/12/2002 | P | PASS |
Tim McCullough
|
|
|
Scheduled by a contractor via Hello! on 08/12/2002 at 06:56:33. Contact: ###-####.
final/ok 8/12/2002 2:52:38 PM
|
Electrical Rough-In | 7/3/2002 | 7/3/2002 | 7/3/2002 | P | PASS |
Jack Frank
|
|
|
r/i ok corrections made
|
Electrical Rough-In | 7/2/2002 | 7/2/2002 | 7/2/2002 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 07/02/2002 at 06:42:12. Contact: ###-####. corrections not made, needs 11/4 inch for cables, and new violation 314.43 no nails in non metallic boxes as code states called 7/2/2002 12:20:27 PM
|
Electrical Rough-In | 7/2/2002 | 7/2/2002 | 7/2/2002 | P | FAIL |
Jack Frank
|
|
|
r/i- rowdy ###-#### called all corrections not made still needs 11/4 inch for cables $45.00 reinspection fee due 7/2/2002 5:19:20 PM
|
Electrical Rough-In | 7/1/2002 | 7/1/2002 | 7/1/2002 | P | FAIL |
Jack Frank
|
|
|
r/i rody ###-#### cor. posted called 314.43, 300.4 11/4 and nail plates, 210.52 (A)(B)needs outlet for wall space in new breakfast dinning area, 250.122 needs #12 pigtails not #14, 314.20 all boxes flush for 1/2 rock and outside boxes BCC all make up shall bo complete 7/1/2002 2:42:13 PM
|