Permit Information
Permit NumberELE04-00856
StatusFinaled
Name ALLSTATE ELECTRIC INC
Site Address 1814 N AMBER ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Service4/5/20044/5/20044/5/2004PPASS
DetailsJack Frank
re inspection of service.; Phone #: ###-#### Internet Inspection Request from: Andy Rose
p/s o/h rec. ok 4/5/2004 12:53:10 PM
Permanent Service3/31/20043/31/20043/31/2004PFAIL
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Andy Rose cor. posted called 110.3(B) and 314.3 exception (1) shall provide bond bushing on metallic conduits in nonmetallic box , do not use old grd rod it is to close to new ones 3/31/2004 2:31:50 PM