Final | 6/30/2005 | 7/1/2005 | 7/1/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/30/2005 at 4:35:57 PM. Contact: ###-####. signed occ card, told owner to change 1 bkr to gfci for people, not equip. ok to final
|
Electrical Rough-In | 6/28/2005 | 6/28/2005 | 6/28/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/28/2005 at 7:17:32 AM. Contact: ###-####. corrections made, ceiling cover ok both floors
|
Electrical Rough-In | 6/27/2005 | 6/27/2005 | 6/27/2005 | P | FAIL |
William E Thomas
|
|
|
###-#### - craig Note: above grid ceiling ballast wiring not protected in accordance with article 300 of the nec
|
Permanent Service | 4/29/2005 | 4/29/2005 | 4/29/2005 | A | PASS |
Bob Reichert
|
|
|
p/s u/g n ok
|
Temporary Service | 4/28/2005 | 4/29/2005 | 4/29/2005 | A | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/28/2005 at 2:54:31 PM. Contact: ###-####. see added inspection 4/29/2005 9:01:56 AM
|
Electrical Rough-In | 4/14/2005 | 4/15/2005 | 4/15/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/14/2005 at 5:10:15 PM. Contact: ###-####. corrections made, ric walls for all and big room clg. 4/15/2005 9:31:31 AM
|
Electrical Rough-In | 4/13/2005 | 4/14/2005 | 4/14/2005 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/13/2005 at 5:15:45 PM. Contact: ###-####. told contr, left corr notice, 300.4(A)(1) & (D) shall provide nail plates and 1 1/4" as code noted states, 250.126 shall use green ground screws 4/14/2005 10:11:58 AM
|
Electrical Rough-In | 3/30/2005 | 3/30/2005 | 3/30/2005 | P | NR |
Bob Reichert
|
|
|
craig - ###-#### called contr and said all make-up to be done and mud rings before inspection 3/30/2005 1:40:07 PM
|
Electrical Rough-In | 12/6/2004 | 12/6/2004 | 12/6/2004 | P | PART |
Bob Reichert
|
|
|
underground conduit inspection please///craig; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cnd u/g for phone only. ok to cover 12/6/2004 12:50:43 PM
|