Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE04-03982
StatusFinaled
Name CAPITOL ELECTRIC
Site Address 6205 W OVERLAND RD
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Alteration: Upsize service and wire printing press
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/1/20052/1/20052/1/2005PPASS
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Jim Williams ok listing for press and corrections made 2/1/2005 12:42:12 PM
Electrical Rough-In1/31/20051/31/20051/31/2005APART
DetailsJack Frank
conference ok
Final1/28/20051/28/20051/28/2005PFAIL
DetailsJack Frank
kim ; Phone #: ###-#### Internet Inspection

Request from: Marsha Smylie cor. posted called, 300.10 bond bushing for REwashers, 314.28, shall provide required distance between raceways, as code noted states, 250.148 tag equip grd to boxes, power for press red taged and turned off,

asked owner frist if press power could be turned off he said yes ETL testing did not follow Boise City process for field testing
1/28/2005 5:00:41 PM 1/28/2005 5:01:11 PM
Permanent Service12/19/200412/20/200412/20/2004APASS
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Jim Williams needs 2 grd rods size bonding to 250.66, remove sprinkler equip from below p/s
p/s u/g rec. ok 12/20/2004 8:28:52 AM