Permit NumberELE05-00068
StatusFinaled
Name ROBERTSON ELECTRIC
Site Address 1065 S ALLANTE PL
Project NameKeller Williams Realty
Customer Number 
ePlanReview 
Description
complete wiring of 16,436" office bld $92,289 JRR 01-07-05///Final cert of value $96,954///4/13/05 BAS
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/7/20054/7/20054/7/2005PPASS
DetailsJack Frank
Scheduled by a contractor via Hello! on 4/7/2005 at 7:30:16 AM. Contact: ###-####. ok card signed 4/7/2005 4:04:26 PM
Electrical Rough-In2/25/20052/28/20052/28/2005APASS
DetailsJack Frank
zane ###-#### 1st floor center section 2/28/2005 8:19:22 AM
Electrical Rough-In2/25/20052/25/20052/25/2005PPASS
DetailsJack Frank
r/i 1st floor center section 2/25/2005 2:30:41 PM
Final2/25/20052/25/20052/25/2005PCANC
DetailsJack Frank
Scheduled by a contractor via Hello! on 2/25/2005 at 8:32:58 AM. Contact: ###-####.///per zane///2/25/05 BAS
Electrical Rough-In2/17/20052/17/20052/17/2005PPART
DetailsJack Frank
Scheduled by a contractor via Hello! on 2/17/2005 at 8:13:57 AM. Contact: ###-####. 2nd floor walls and hard ceilings ok 2/17/2005 2:42:15 PM
Rough-In Permanent Service2/8/20052/9/20052/9/2005APASS
DetailsJack Frank
Scheduled by a contractor via Hello! on 2/8/2005 at 8:02:52 PM. Contact: ###-####. u/g ok p/s u/g new ok 2/9/2005 8:24:10 AM
Rough-In Permanent Service2/8/20052/8/20052/8/2005PFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 2/8/2005 at 9:07:31 AM. Contact: ###-####. stop work posted u/g parking lot done by excavation contractor called electrical contractor,also talked to his man on site and talked with general at job site 2/8/2005 2:11:18 PM
Electrical Rough-In2/3/20052/3/20052/3/2005PPART
DetailsJack Frank
Scheduled by a contractor via Hello! on 2/3/2005 at 7:32:09 AM. Contact: ###-####. north section of building walls and hard ceilings ok 2/3/2005 4:02:24 PM
Rough-In Permanent Service2/1/20052/2/20052/2/2005PFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 2/1/2005 at 10:25:19 AM. Contact: ###-####. cor. and do not cover posted met contractor,310.15(B)(2)(a) derate conductorsin ENT,110.3(A) replace damaged MC, 250.24 terminate GRC at neutral bus not equip grd bus,362.26 shall not be more than 360 degrees of bends ENT250.70 shall use grd clamp listed for size GEC 620.23(A) shall provide seperate circuit for elevator machine rm lights and recepts soffit only ok for cover reinspection fee due posted 2/2/2005 2:51:29 PM
Permanent Service1/28/20051/28/20051/28/2005PFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 1/28/2005 at 11:09:06 AM. Contact: ###-####. corrections not made same cor. posted called also reinspection fee due posted 1/28/2005 4:02:37 PM
Permanent Service1/27/20051/27/20051/27/2005PFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 1/27/2005 at 9:21:10 AM. Contact: ###-####. cor. posted needs bond strap, grd water system 1/27/2005 3:55:09 PM
Electrical Rough-In1/10/20051/10/20051/10/2005PPART
DetailsJack Frank
zane ###-#### r/i ok east section ok buildind walls and ceiling 1/10/2005 3:21:07 PM