Final | 2/17/2005 | 2/18/2005 | 2/18/2005 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Nikki Day corrections made, ok to final 2/18/2005 10:13:00 AM
|
Electrical Rough-In | 2/10/2005 | 2/11/2005 | 2/11/2005 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/10/2005 at 4:56:31 PM. Contact: ###-####. 110.26(A)(1) depth of work space shall be 3', 358.26 there shall be max 360 degree bends, 348.30 fmc shall be supported witin 12" of box, 210.63 gfci shall be provided on roof for refrigeration units, 110.3(B) equipment shall be listed 2/11/2005 11:51:54 AM
|