Permit NumberELE05-02222
StatusFinaled
Name ENTERPRISE ELECTRIC
Site Address 4145 N JONES AVE
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/16/20063/17/20063/17/2006PPASS
DetailsBob Reichert
NEED FINAL ON HOT TUB. WILL LEAVE NORTH GATE OPEN, PLEASE MAKE SURE ITS CLOSED AFTER. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok to final
Final8/11/20058/12/20058/12/2005ANR
DetailsBob Reichert
FINAL FOR HOT TUB; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH hot tub still needs 3rd party evaluation or replaced. called contr.
Final8/9/20058/10/20058/10/2005PFAIL
DetailsJack Frank
final inspect for branch panel & hot tub circuit; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
cor. posted called hot tub wired to canadian standards shall replace or have it tested by testing lab for US standards, 680.26(C) use min. #8 solid for bonding, 680.22(A)(3) outlet shall be no closer than 10FT no further than 20ft
Final8/8/20058/9/20058/9/2005PNR
DetailsBob Reichert
WIRING FOR BRANCH PANEL & HOT TUB CIRCUIT.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH met elect, talked about 90's, clearances, and not being ready for inspection