DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/20/20059/20/20059/20/2005APASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok to final
Final8/30/20058/30/20058/30/2005PPART
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called contr to make gnd wire green and use 30A Switch for hot water disc. will do final after signs are up. signed occ card
Final8/29/20058/30/20058/30/2005AFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called contr,210.8(B)(1) bathroom shall use gfci rcpts,422.31 disc for water heater shall be provided,408.4 panel schedule shall be provided, 250.104 metal water piping shall be bonded
Permanent Service8/16/20058/17/20058/17/2005PPASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen p/s u/g n ok
Permanent Service8/16/20058/17/20058/16/2005ACANC
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen Inspection cancelled from web by: Ryan Christensen
Electrical Rough-In8/1/20058/2/20058/2/2005APASS
DetailsWilliam E Thomas
ryan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
Electrical Rough-In7/29/20057/29/20057/29/2005AFAIL
DetailsBob Reichert
rough in to cover seth is contact; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen talked to contr, left corr notice, do not cover card on panel. 110.26(F)(1) no piping shall be in dedicated electrical space over meter can, 348.30(A) fmc shall be strapped within 12" of box, 300.4(A)(1) raceways shall be min 1 1/4" from edge of framing member or shall be protected by steel plates
Electrical Rough-In7/27/20057/28/20057/28/2005APASS
DetailsBob Reichert
inspect the ufer ground for cover; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok to cover gec
Electrical Rough-In7/27/20057/27/20057/27/2005PPASS
DetailsBob Reichert
underground seth ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to cover u/g to pole bases and to cover gec
Electrical Rough-In7/26/20057/26/20057/26/2005PCANC
DetailsMike Kinnear
seth-- underground; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie contractor called canc. inspection
Electrical Rough-In7/25/20057/26/20057/26/2005APASS
DetailsBob Reichert
ryan - Note: lightpole bases; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to pour pole bases only. Need to see u/g to bases from source of power.
Temporary Service7/21/20057/22/20057/22/2005ACANC
DetailsBob Reichert
forman on job is seth woodward; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen wrong permit number