Permit Information
Permit NumberELE05-02676
StatusFinaled
Name DOHERTY ELECTRIC
Site Address 3100 W CRESCENT RIM DR
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Alteration: run new wiring, conduits, boxes, recps., lights.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/1/20059/1/20059/1/2005APASS
DetailsJack Frank
ok
Conference8/18/20058/19/20058/22/2005ADONE
DetailsJack Frank
talked with state elevator inspector and electrical contractor will post post correction , light and recept in elevator equip rm shall be dedicated circuit, and terminate flex from new cabinet to equip
Final8/18/20058/18/20058/18/2005PCANC
DetailsJack Frank
Re-insp.; Phone #: ###-#### Internet Inspection Request from: Heather Packer waiting for information from state elevator inspector, and fire alarm inspector
Final8/17/20058/17/20058/17/2005PFAIL
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Heather Packer cor called 300.10 needs bond bushing where RE washers are used, 250.148 grd 4sq box, label elevator disconnects, also elevator equip rm all messed up circuit for recept messed up I will address items with owner