Permit NumberELE05-03104
StatusFinaled
Name ENTERPRISE ELECTRIC
Site Address 8119 W USTICK RD
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: remodel////Final cert of value $9,000 12/22/2005 cmc
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/15/200511/18/200511/18/2005APASS
DetailsBob Reichert
CORRECTIONS MADE PER NOTE, BRAD WILL BE ON-SITE, ###-####. THANK YOU; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok to final
Final11/2/200511/3/200511/3/2005PFAIL
DetailsBob Reichert
MAJOR REMODEL; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr, left corr notice, 408.4, panel schedule needs completed, 358.30(A) emt shall be supported,230.70(B) service disc shall be marked,800.52(B)shall remove abandoned cables,and install from struct part of bldg
Final10/19/200510/20/200510/20/2005APART
DetailsBob Reichert
WE ARE READY FOR A FINAL INSPECTION SO THAT THE TENANT CAN GET OCCUPANCY FOR THE MAIN FLOOR. ANY QUESTIONS, PLEASE FEEL FREE TO CALL US. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr, left corr notice, signed t/o card, NEC 110.3 front ceiling fixtures shall be installed and lower level completed. Note: no access beyond front nw office area shall be permitted. Construction and t/o expire 11-04-05.
Final10/14/200510/17/200510/17/2005AFAIL
DetailsBob Reichert
READY FOR FINAL INSPECTION FOR THE UPSTAIRS FOR OCCUPANCY. YOU CAN CONTACT THE CONTRACTOR ON HIS CELL PHONE AT ###-####. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr, left correction notice, 404.9 switches shall have faceplates, 406.4 recpt shall be securely fastened,406.5 recpts shall have faceplates, 406.8(E) floor recpts shall have weatherproof covers, 314.25 boxes shall have covers, 110.12(C) there shall be no broken parts, 110.3 recpts shall be installed correctly,i.e. no hot and gnd reversed, no hots on neutrals, front recpts shalll operate, 210.8(B) gfci recpts shall be provided by sinks
Final10/7/200510/10/200510/10/2005ACANC
DetailsBob Reichert
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa see conf
Conference10/10/200510/10/200510/10/2005ADONE
DetailsBob Reichert
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa met with general, they are still at least 1 week out. Told them they need to be all but done before they ask for t/o
Electrical Rough-In9/26/20059/27/20059/27/2005APASS
DetailsBob Reichert
R/I FOR COVER IN LAB AREA. BRAD IS ELECT. LH Internet Inspection Request from: BRIAN KEITH ok to cover walls only lab area
Electrical Rough-In9/13/20059/14/20059/14/2005PPASS
DetailsBob Reichert
REINSPECT ROUGHIN WORK, LATE PM PLEASE. BRAD IS ON THE JOB IN AFTERNOON. THANK YOU; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH talked about clean up of exst bldg and they need to bring up to code. ric ok for walls only.
Electrical Rough-In9/2/20059/6/20059/6/2005AFAIL
DetailsBob Reichert
rough in re-inspect ready. ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corrections not made, called contr, left same corr notice, fee due
Electrical Rough-In9/1/20059/1/20059/1/2005PNR
DetailsJack Frank
rough in ready for inspect this after noon, Brad Parton is on the job. Thank you; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH electrical contractor ok do not cover and correction posted for low voltage contractor to bld05-01608
Electrical Rough-In8/24/20058/25/20058/25/2005ANH
DetailsBob Reichert
electric rough in. thank you; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called and said to re-schedule