Permit Information
Permit NumberELE05-03484
StatusFinaled
Name R0SEMARIE WIMER & GAYLE R EATON
Site Address 1513 S TANAGER WAY
Project Name 
Customer Number 
ePlanReview 
Description
per jim schmer remove re-insp fee which was added on 11/10/05/mls/12/2/05
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/10/200511/14/200511/14/2005APASS
DetailsJack Frank
###-####--gayle--call 1st before insp for homeowner ok card signed
Final11/10/200511/10/200511/10/2005PFAIL
DetailsJack Frank
gayle; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa not ready no power to shop reinspection fee
Final11/9/200511/9/200511/9/2005PPART
DetailsJack Frank
gayle; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa r/i ok corrections made, still needs to terminate GEC to equip grd bus 250.32(B)(1)
Final11/7/200511/7/200511/7/2005PFAIL
DetailsJack Frank
gail ###-#### cell cor. met owner 250.32(B)(1) isolate grds and neuts at shop service 300.4 nail plates and 11/4" 314.16 box fill, 210.70 needs outside for exit door, 314.17 conn for bell box, remove devices from boxes so I can inspect
Electrical Rough-In9/26/20059/27/20059/27/2005APASS
DetailsJack Frank
underground trench inspection ///gayle; Phone #: ###-#### Internet Inspection Request from: Barbara electrode ok for dirt cover
Electrical Rough-In9/23/20059/26/20059/26/2005APART
DetailsJack Frank
trench inspection//gayle; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa electrode for concrete, and u/g
Electrical Rough-In9/23/20059/23/20059/23/2005PFAIL
DetailsJack Frank
trench inspection//gayle; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa conference ok only owner needs concrete encased electrode at new shop, and u/g, has over 360 degrees of bends, and shall be 18" below grade where not under concrete