Final | 10/25/2005 | 10/25/2005 | 10/25/2005 | P | PASS |
Mike Kinnear
|
|
|
joel; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok final
|
Permanent Service | 10/24/2005 | 10/25/2005 | 10/25/2005 | A | FAIL |
Mike Kinnear
|
|
|
JOEL//please call 30 min prior; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ground wire from water pipe has to go to main service. bond hot & cold water pipes
|
Permanent Service | 10/25/2005 | 10/25/2005 | 10/25/2005 | P | PASS |
Mike Kinnear
|
|
|
joel; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s o/h reconnect ok
|
Final | 10/20/2005 | 10/20/2005 | 10/20/2005 | P | FAIL |
Mike Kinnear
|
|
|
joel; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/w owner he needs an electrical contractor to do service. sub panal so messed up it needs to be replaced. (note almost all the bottom of panal cut out. grounds & neut. not sperated) can not run 4 wires for service connection, needs to be 3 wires sun light resistant type. grounding not done correct (needs #6cu wire to ground rods) need to connect water system for grounding electrode.
|