Permit Information
Permit NumberELE05-04010
StatusFinaled
Name TRI-STATE ELECTRIC
Site Address 2007 N CRIBBENS ST
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: Wire 3 bedroom homes for habitat for humanities
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/31/20065/31/20065/31/2006PPASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung corrections made, ok to final
Final5/30/20065/31/20065/31/2006AFAIL
DetailsBob Reichert
call first ; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung called contr, left corr notice, nec 352.30(A) rnc shall be supported within 3' of panel,250.64(B) gec shall be secured to surface, 408.4 circuit directory shall be provided,110.3(B) disposal shall be wired, reverse polarity on recpt on island shall be corrected, 422.31(B) furnace disconnect shall be supplied
Permanent Service5/2/20065/3/20065/3/2006APASS
DetailsBob Reichert
kelly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok
Electrical Rough-In11/23/200511/23/200511/23/2005APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 11/23/2005 at 7:29:25 AM. Contact: ###-####. ric ok, corrections made
Electrical Rough-In11/7/200511/7/200511/7/2005PFAIL
DetailsBob Reichert
kelly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles no panel set, talked to elect, left corr notice, 210.52(A)(2) recpt shall be added in entry area wall, 210.52(F) recpt shall be added at rear of dwelling, 314.20 boxes shall be flush with combustible material, 334.30 nm cable shall be supported within 12" of boxs, 300.4(A)(1) edge of bored hole shall be 1 1/4" from edgfe of framing member, 800.133(A)(1) comm cable shall not be run with power cables