Permit NumberELE05-04112
StatusFinaled
Name A-1 ELECTRIC
Site Address 14086 W TALON CREEK DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/8/20062/9/20062/9/2006APASS
DetailsBob Reichert
Brian; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong corrections made, ok to final
Final2/8/20062/8/20062/8/2006PFAIL
DetailsBob Reichert
dan; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left corr notice, 680.73 electrical equipment for tub shall be accessible without damaging building, 406.5 recpt faceplate shall seat against mounting surface (upper bath), 406.4 recpts shall be securely fastened in place(front room, north side), 110.3(B) listed equipment shall be installed in accordance with instructions(mbr closet light lens)
Rough-In Permanent Service11/14/200511/15/200511/15/2005APASS
DetailsBob Reichert
brian ; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr made, ric ok, p/s u/g n ok
Rough-In Permanent Service11/14/200511/14/200511/14/2005PFAIL
DetailsBob Reichert
brian ###-#### called contr, left corr notice, 300.4(A)&(D) 1 1/4" shall be maintained for bored holes and nm cable shall be from edge of framing member, 800.133(A)(1) comm cable shall not be run with class 1 wiring,110.12(A) there shall be no open wiring holes in boxes, 314.20 boxes shall be flush with combustibloe material (out back recpt), BCC job id sticker shall be posted