Permit Information
Permit NumberELE05-04401
StatusExpired
Name A M E ELECTRIC
Site Address 1770 N FISK ST
Project Name 
Customer Number 
ePlanReview 
Description
12/6/2005 - (United Water) install 400 amp switch gear w/ 1-200 VFD - $25,775.00 per initial cert of value - cmc
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
ELE-Aging Inspection3/4/20083/4/20083/6/2008 DONE
DetailsBob Reichert
no work being done, see doc expire
DOC - Permit Expired3/6/20083/6/20083/6/2008APASS
DetailsBob Reichert
see aging, no work being done
ELE-Aging Inspection1/3/20081/3/20081/11/2008 DONE
DetailsBob Reichert
may need to wait till spring for access
ELE-Aging Inspection10/10/200710/10/200710/16/2007 DONE
DetailsBob Reichert
called, left message to call to set up final
ELE-Aging Inspection1/19/20071/19/20071/19/2007 DONE
DetailsBob Reichert
called to set up request for final injspection
ELE-Aging Inspection10/2/200610/2/200610/2/2006 PART
DetailsJack Frank
called
ELE-Aging Inspection4/4/20064/4/20064/4/2006 PART
DetailsJack Frank
called contractor he will check status, and schedule final
Rough-In Permanent Service1/24/20061/24/20061/24/2006PPASS
DetailsJack Frank
Mike (A M E Electric office ###-####) -- Jack Frank scheduled to meet at 12 pm (noon) -- call 1st before insp; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong r/i ok check grds for other system and electrodes at final p/s o/h rec. ok
Conference1/23/20061/24/20061/24/2006ANH
DetailsJack Frank
Scheduled by a contractor via Hello! on 1/23/2006 at 5:04:02 PM. Contact: ###-####. notice posted called
Rough-In Permanent Service1/23/20061/24/20061/24/2006ANH
DetailsJack Frank
Scheduled by a contractor via Hello! on 1/23/2006 at 5:03:15 PM. Contact: ###-####. notice posted called
Rough-In Permanent Service1/20/20061/20/20061/20/2006PFAIL
DetailsJack Frank
Mike; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong cor. fee due posted called more violations created from 1st correction posted, 250.102(C) shall size bond jumper to 250.66, 408.36(F) back fed device clip 120/230 V panel, 300.4 (F) bushings for 4 and larger, 300.10 tighten grd choke fittings, nipples from LBs shall have locknuts both sides of cabinet and be made up tight, everything is loose, 110.12(A) seal all unused KOs
Conference1/16/20061/16/20061/17/2006PDONE
DetailsJack Frank
Scheduled by a contractor via Hello! on 1/16/2006 at 8:16:15 AM. Contact: ###-####.
Rough-In Permanent Service1/16/20061/16/20061/17/2006PFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 1/16/2006 at 8:15:27 AM. Contact: ###-####. cor. called 314.28(A)(3) LBs too small, 200.6 shall not ID 6 or smaller neutral, 250.53,56 needs 2 grd rods, 250.24(A)(1) all GEC shall terminate at neutral bus, 250.90,92 shall bond nipples line side of p/s also bond both ends of GEC in pipe