Permit Information
Permit NumberELE05-04467
StatusFinaled
Name PEAK ELECTRIC
Site Address 5602 W STATE
Project NamePLANTATION PLAZA
Customer Number 
ePlanReview 
Description
12/12/2005 (HUMAN BEAN) Power & lightig for Drive-thru coffee house - $11,820 per initial cert of value - cmc ///Final value is $13,848//5/17/06 LEG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/10/20064/11/20064/11/2006APASS
DetailsBob Reichert
Re-inspect for final on pole lights.; Phone #: ###-#### Internet Inspection Request from: todd hall corr made, ok to final, no card to sign
Final4/7/20064/10/20064/10/2006AFAIL
DetailsBob Reichert
INSPECTION FOR EXTERIOR PARKING LOT LIGHTING (POLE LIGHTS); Phone #: ###-#### Internet Inspection Request from: todd hall called contr, 250.86 poles shall be grounded, did not leave corr notice, told contr to recall when done.
Final3/30/20063/30/20063/30/2006PPART
DetailsBob Reichert
Final inspect for building only, inspect of remaining items and for items on correction notice. Customer would like CofO for building. Pole lights yet to come. Please call Todd with results. ###-####; Phone #: ###-#### Internet Inspection Request from: todd hall t/o card signed by 336, called left message that we will final later
Electrical Rough-In3/20/20063/21/20063/21/2006APASS
DetailsBob Reichert
Todd -- call 1st before insp; prefer 11:00 AM; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong north side drive ok to cover, corrections made
Electrical Rough-In3/20/20063/20/20063/20/2006PNR
DetailsBob Reichert
Todd -- underground conduit for north end of property; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, u/g not dug deep enough yet
Electrical Rough-In3/16/20063/16/20063/16/2006PPART
DetailsBob Reichert
Todd -- reinspection for underground; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, left message, said east part of driveway ok to cover, but north part still not deep enough. Left "cover ok" sticker on panel. left corr notice posted
Final3/14/20063/15/20063/15/2006APART
DetailsPat Lass
Re-inspect for final on building only. Pole lights and sign to be finished when pole lights arrive in approximately one week. Customer would like to move in and begin serving coffee soon.Please call if any questions.; Phone #: ###-#### Internet Inspection Request from: todd hall
I signed T/O.
directory and underground still not corrected.
Final3/13/20063/14/20063/14/2006AFAIL
DetailsBob Reichert
please look at trench work also///Phone #: ###-#### Internet Inspection Request from: todd hall called contr, left corr notice,210.63, shall provide 125 v single phase recpt (gfci) for rooftop, 300.5 u/g shall be 24" under drive, 110.3(B) gfci shall operate,408.4 panel sched shall be complete
Electrical Rough-In3/6/20063/7/20063/7/2006APART
DetailsPat Lass
Inspect for site light pole bases.; Phone #: ###-#### Internet Inspection Request from: todd hall
2 pole bases ok
Permanent Service2/24/20062/24/20062/24/2006PPASS
DetailsBob Reichert
re-inspect for perm service. Bob, please inspect asap as per our conversation this am. Please call me as soon as you have an idea when you can inspect so I can call IDPCO to let them know when to re-connect. Thank you.; Phone #: ###-#### Internet Inspection Request from: todd hall p/s reconnect o/h ok
Permanent Service2/23/20062/23/20062/23/2006PNR
DetailsBob Reichert
Inspection for perm service. Meter can on pole. Please inspect after 2:00pm and before 3:30pm if possible. IDPCO can re-connect at about 4-4:30pm. Please call if any schedule issues.; Phone #: ###-#### Internet Inspection Request from: todd hall contr way behind and told him to re-call for inspection
Electrical Rough-In1/19/20061/19/20061/19/2006PPASS
DetailsJim Schmer
re-inspect for rough-in. Please look at the UFER installation at the drain out along the South wall; Phone #: ###-#### Internet Inspection Request from: todd hall ufer ok, tied to rebar by drain, r/i ok correction made jms
Electrical Rough-In1/18/20061/19/20061/19/2006AFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: todd hall met elect, left corr notice, 300.4(A) & (D) 1 1/4" for holes and mc casble shall be maintained, 110.12(C) there shall be no damaged parts, 330.30(B) mc cable shall be strapped within 12" of box
Electrical Rough-In1/5/20061/5/20061/5/2006PPART
DetailsBob Reichert
underground- todd; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie u/g fom bldg east to light pole, and so toward chinden ok to cover
Electrical Rough-In12/20/200512/20/200512/20/2005PCANC
DetailsBob Reichert
todd Note: ufier; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles cancelled to concrete
Electrical Rough-In12/12/200512/13/200512/13/2005PPART
DetailsBob Reichert
###-#### - todd Hall Note: underground u/g under bldg only ok to cover, need to see rest later