Permit Information
Permit NumberELE05-04525
StatusFinaled
Name KEN JOHNSTON
Site Address 1917 S BROADMOOR DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/14/20064/14/20064/14/2006PPASS
DetailsJack Frank
ken; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
Electrical Rough-In1/9/20061/10/20061/10/2006APASS
DetailsJack Frank
KEN nOTE: PLEASE CALL 1/2 HR IF PR0BLEM; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
r/i ok
Electrical Rough-In1/9/20061/9/20061/10/2006PFAIL
DetailsJack Frank
please call prior to inspection///ken; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. not made terminate GEC to p/s not subpanel
Electrical Rough-In1/4/20061/4/20061/4/2006PFAIL
DetailsJack Frank
ken ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles cor. do not cover, called 210.52(A&B) needs out in new bedrm 2ft wall, all outlets in din rm shall be kit circuit, 210.52(C) countertop outlet spacing, 314.17 replace boxes with broken clamps, 250.148 splice all equip grds together at boxes, 250.52(A)(1) grd u/g water pipe 5ft300.10&12 4 locknuts for rigid nipple p/s subpanel, 300.4(A)(1)(D) all locations, 110.12 seal all unused KOs no tin can lids to be used 230.28 guy kit mast,312.5 conn for GEC, remove GEC from subpanel