Permit Information
Permit NumberELE06-00103
StatusFinaled
Name A-1 ELECTRIC
Site Address 5463 N EBBETTS AVE
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Temporary Service1/11/20061/12/20061/12/2006APASS
DetailsBob Reichert
brian --re-insp; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corrections made, t/s u/g n ok
Temporary Service1/11/20061/11/20061/11/2006PFAIL
DetailsBob Reichert
brian -###-#### called contr, left corr notice, 250.53(G) rod electrode shall be such that upper end is flush with or below gnd, 250.24(A)(1) gndg electrode conductor shall be connected to gnded conductor bus,110.14(A) connections shall be tight,110.3(B) equipment shall be installed per instructions,all screws provided, 250.52(A)(5)(b) steel electrode shall be at least 5/8" diameter, fee due