Permit Information
Permit NumberELE06-00105
StatusFinaled
Name DOHERTY ELECTRIC
Site Address 4118 N MOUNTAIN VIEW DR
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Alteration: 2 room
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/24/20077/26/20077/26/2007PPASS
DetailsBob Reichert
Final - pls call Jim w/Doherty @ ###-#### 30min prior so that he can meet the inspector to walk through - Jim will be 2 houses down from there. Scheduled by Heather w/Doherty Phone #: ###-#### Internet Inspection Request from: Heather Packer met contr, ok to final
Permanent Service1/18/20061/18/20061/18/2006PPASS
DetailsJack Frank
Call Tim 1/2hr before for access; Phone #: ###-#### Internet Inspection Request from: Heather Packer p/s u/g rec. ok
Electrical Rough-In1/17/20061/18/20061/18/2006APASS
DetailsJack Frank
wall cover--pls call Tim 1/2 hr before for access ###-####; Phone #: ###-#### Internet Inspection Request from: Heather Packer ok
Permanent Service1/16/20061/17/20061/17/2006AFAIL
DetailsJack Frank
Please call 1/2 before for access - Tim ###-####; Phone #: ###-#### Internet Inspection Request from: Heather Packer see r/i notes
Electrical Rough-In1/16/20061/17/20061/17/2006AFAIL
DetailsJack Frank
Please call 1/2 before for access - Tim ###-####; Phone #: ###-#### Internet Inspection Request from: Heather Packer
cor. called 314.16 box fill 300.4 nail plates and 11/4", 250.66 all grds and bond #$, 250. 52(A)(1) or 104(A)(1) grd or bond water system 250.24 (A)(1) all grds and bonds shall terminate at neutral bus, 250.90,92 bond all raceways and nipples at p/s with #4, 250.56 needs 2 grd rods