Permit Information
Permit NumberELE06-00116
StatusFinaled
Name ROMAR ELECTRIC
Site Address 1450 N KIMBALL ST
Project NamePeterson Autoplex Body Shop
Customer Number 
ePlanReview 
Description
Electrical Permit - New: PROVIDING WIRING FOR NEW SHOP INCLUDING NEW LIGHTNG AND GEAR
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/28/20069/29/20069/29/2006APASS
DetailsBob Reichert
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections made, equipment labelled, ok to final, signed card
ELE-Aging Inspection8/28/20068/28/20068/29/2006 DONE
DetailsBob Reichert
called, they may want to evaluate 2 jobs for same owner, elect will check
Final6/27/20066/28/20066/28/2006PCANC
DetailsBob Reichert
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see conf
Conference6/28/20066/28/20066/28/2006PDONE
DetailsBob Reichert
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met contr, air comp supplier, gen to discuss listing for air comp
Final6/20/20066/20/20066/20/2006PFAIL
DetailsBob Reichert
BCC 4-05-33(A)(B) equipment shall be listed and labelled by a nationally recognized testing lab (air comp)
Final5/25/20065/25/20065/26/2006PPART
DetailsBob Reichert
mike ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie looked at recpts,they need to wire hot water heater, air comp, finish strapping conduit, install counter in front, install approved egress lights, ensure listing for paint boothes. I wouldn't sign t/o, said to finish and call for final inspection. Posted correction notice 5-26-06. Signed t/o card
Electrical Rough-In5/11/20065/11/20065/11/2006PPART
DetailsBob Reichert
mike Note: ceiling; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover ceilings, office areas only
Permanent Service5/8/20065/8/20065/8/2006PPASS
DetailsBob Reichert
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok
Permanent Service5/2/20065/2/20065/2/2006PFAIL
DetailsBob Reichert
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles talked w/contr, left corr notice, nec 314.28 (A)(2) pull and junction box shall be sized for angle pulls- not less than 16" opposite wall of 2" conduits
Electrical Rough-In4/17/20064/18/20064/18/2006APASS
DetailsBob Reichert
Mike; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong walls and hard lids ok to cover only
Conference4/18/20064/18/20064/18/2006ADONE
DetailsJack Frank
Mike; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong reviewing prints of classified area , still needs documentation?
Electrical Rough-In4/10/20064/10/20064/10/2006PNR
DetailsBob Reichert
Mike; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong they received data on air changes, not classification for hazardous area. They called architect, I explained what we need, he said that Electrical engineer should provide the area classification per 500.4.
Electrical Rough-In4/5/20064/5/20064/5/2006PNR
DetailsBob Reichert
Mike -- for wall; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong they don't have classification areas defined per 500 (4), met with contr and builder and told them that engineer must classify hazardous areas
Electrical Rough-In4/3/20064/4/20064/5/2006PNR
DetailsBob Reichert
Mike -- wall rough in; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong wrote correction, 500.4(A) all areas designated as hazardous (classified) locations shall be properly documented. This documentation shall be available ffor users.
Electrical Rough-In3/7/20063/8/20063/8/2006APART
DetailsJack Frank
Mike -- underground; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong u/g for office area only needs documuntation for repair garage and spray booth areas
Electrical Rough-In1/13/20061/13/20061/13/2006PPASS
DetailsBob Reichert
underground insp - mike ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie u/g for conduit south side bldg ok to cover.
Electrical Rough-In1/12/20061/13/20061/13/2006APASS
DetailsBob Reichert
grounding inspection//mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa gec only ok to backfill
Electrical Rough-In1/12/20061/12/20061/12/2006PPASS
DetailsBob Reichert
THIS IS FOR A UFER INSPECTION - ANY QUESTIONS PLEASE CALL MIKE HICKS; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok to cover gec, need to see before backfill
Electrical Rough-In1/11/20061/12/20061/12/2006ACANC
DetailsBob Reichert
ANY QUESTIONS PLEASE CALL MIKE HICKS-THIS IS FOR A UFER INSPECTION; Phone #: ###-#### Internet Inspection Request from: Jeff Radford do in pm